GEH-702 Users Manual

37



Register Address

Variable

Value

Factory Default

Read/Write






267






Power Reversal Pickup

1 - 10

2 - 20

3 - 30

4 - 40

5 - 50

6 - 60

7 - 70

8 - 80

9 - 90

10 - 100

11 - 110

12 - 120

---- [10x read value]

67 - 670

68 - 680






1






Read/Write

268

Power Reversal Delay

0 - Off

1 - 1

2 - 2

3 - 3

4 - 4

5 - 5

6 - 6

7 - 7

8 - 8

9 - 9

10 - 10 11- 11

12 - 12 13 - 13 14 - 14 15 -15

0

Read/Write

269

Power Direction Setting

0 - Line to Load

1 - Load to Line

0

Read/Write



270



Power Demand Interval

1 - 5 minutes

2 - 10

3 - 15

4 - 20

5 - 25

---- [5x read value]

12 - 60



5



Read/Write



271



Relay1 (Output1) Function

0 - None

1 - Group 1

2 - Group 2

3 - Group 3

4 - Group 4

5 - Group 5

6 - Group 6



0



Read/Write

272

Relay2 (Output2) Function

0 - None

1 - Group 1

2 - Group 2

3 - Group 3

4 - Group 4

5 - Group 5

0

Read/Write

275

Input 1

0 - None

1 - Trip

2 - RELT

0

Read/Write