GEH-702 Users Manual


Table 29. Communication Parameters: Modbus Function 5

Register

Parameter

Value

Read/Write

101

Save Data

Write

103

Save Real Time Clock Registers

Write

104

Read Real Time Clock Registers

Write

106

Defeat Ground Fault

0 – OFF

1 – ON

Write

108

Trip Breaker

1 – Trip

Write

112

Relay 1 state

1 – ON

0 – OFF

Read/Write

113

Relay 2 state

1 – ON

0 – OFF

Read/Write

114

ZSI-Out

1 – ON

0 – OFF

Read/Write

115

Clear Power Demand

1 – Clear

Write

116

Clear All Events

1 – Clear

Write

117

Clear EEPROM

1 – Clear

Write

118

Clear Energy Total

1 – Clear

Write

119

Clear All Trip Counters

1 – Clear

Write

120

Clear LT Trip Counter

1 – Clear

Write

121

Clear All Pickup Counters

1 – Clear

Write

122

Clear Short Time Trip Count

1 – Clear

Write

123

Clear Instantaneous Trip Count

1 – Clear

Write

124

Clear Ground Sum and CT Fault Trip Counts

1 – Clear

Write

125

Clear Rating Plug Too Small Count

1 – Clear

Write

126

Clear Power Reversal Trip Count

1 – Clear

Write

127

Clear Voltage Unbalance Trip Count

1 – Clear

Write

128

Clear Under Voltage Trip Count

1 – Clear

Write

129

Clear Current unbalance Trip Count

1 – Clear

Write

130

Clear Overvoltage trip Count

1 – Clear

Write

131

Clear Over Temperature Trip Count

1 – Clear

Write

132

Clear ROM CRC fault count

1 – Clear

Write

135

Clear Metering Data

1 – Clear

Write

143

Trigger Waveform Capture

1 – Clear

Write

144

Clear Waveform Capture Data Buffer

1 – Clear

Write

145

Clear Preventive Maintenance data

1 – Clear

Write

148

Clear STO trip count

1 – Clear

Write

149

Clear Comm. trip count

1 – Clear

Write