GE Industrial Solutions Spectra RMS Molded Case User Manual

Page 30

Advertising
background image

GEH-702 Users Manual

29


Table 25. Discrete Input, Function Code 2

Register

Parameter

Value

0

Long time pickup state

0 - Out 1 - In

1

Short time pickup state

0 - Out 1 - In

2

GF Sum Pickup state

0 - Out 1 - In

3

ZSI IN active

0 - On

1 - Off

4

ZSI-Out active (Output 3)

0 - On

1 - Off

5

Relay 1 Status (Output 1)

0 - On

1 - Off

6

Relay 2 Status (Output 2)

0 - On

1 - Off

8

GF Defeat

0 - On

1 - Off

9

Input 1 Status

0 - On

1 - Off

11

Relt Status

0 - Off

1 - On

21

Voltage Unbalance Status

0 - Normal

1 - Pickup

22

Under Voltage Status

0 - Normal

1 - Pickup

23

Over Voltage Status

0 - Normal

1 - Pickup

24

Current Unbalance Status

0 - Normal

1 - Pickup

25

Power Reversal Status

0 - Normal

1 - Pickup

27

Breaker position

0 - Open

1 - Closed

51

MET Tripped

0 - No

1 - Yes

54

WFC Data Available

0 - No

1 - Yes

56

Voltage Unbalance Alarm Status

0 - Normal

1 - Alarm

57

Under Voltage Alarm Status

0 - Normal

1 - Alarm

58

Over Voltage Alarm Status

0 - Normal

1 - Alarm

59

Current Unbalance Alarm Status

0 - Normal

1 - Alarm

60

Power Reversal Alarm Status

0 - Normal

1 - Alarm

61

GF Sum Alarm Status

0 - Normal

1 - Alarm

63

Load Shedding Status

0 - Normal

1 - Alarm

65

Diagnostic Mode status

0 - Off

1 - On

66

Defeatable GF

0 - Off

1 - On