GEH-702 Users Manual

25


Appendix A. Display Screen Flow

Table 20. Setup Mode Programming

Function

Title (as implemented)

Min. Value

Max. Value

Default Setting

Setting Choices

Language

LANGUAGE

ENGLISH

FRANÇAIS

ENGLISH

English, Français, Español,Deutsch, Chinese

Long Time

LONG TIME PICKUP

0.5

1.0

1.0

0.50X to 1.00X steps of 0.05X

LONG TIME DELAY BAND

MVT1

F7

CB 6

MVT1-4, C1-C10, F1-F7

(Max. values vary by frame)

Short Time

SHORT TIME PICKUP

1.5

9.0

1.5

1.5C to 9.0C steps of 0.5C

SHORT TIME DELAY BAND

1

12

5

1 to 12 time bands

SHORT TIME SLOPE

0

3

0

0 to 3

Instantaneous

INSTANTANEOUS PICKUP

2.0

25.5

2.0

2.0X to 14.0X steps of 0.5X

15.0X to 19.0X steps of 1.0X

20.5X to 25.0 steps of 1.5X

25.5X (Max. values vary by frame)

Reduced Energy

Let Through

RELT INST PICKUP

1.5

10

1.5

1.5X to 10.0X steps of 0.5X



Ground Fault

GF TRIP PICKUP

0.4

1.0

1.0

0.4S to 1.0S steps of 0.05S

GF TRIP DELAY BAND

OFF

15

5

OFF or 2 to 15 time bands

GF TRIP SLOPE

0

3

0

0 to 3

GF ALARM PICKUP

0.4

1.0

1.0

0.4S to 1.0S steps of 0.05S

GF ALARM DELAY BAND

OFF

15

5

OFF or 2 to 15 time bands

GF ALARM SLOPE

0

3

0

0 to 3



Zone Selective

Interlock

ZONE SEL INTLK

OFF

GF/ST/INST

OFF

GF, GF/ST, ST, ST/INST, GF/ST/INST

ZSI ST PICKUP

1.5

9.0

1.0

1.5C to 9.0C steps of 0.5C

ZSI ST DELAY BAND

1

12

6

1 to 12 time bands

ZSI ST SLOPE

0

3

0

0 to 3

ZSI GF PICKUP

0.4

1.0

1.0

0.4S to 1.0S steps of 0.05S

ZSI GF DELAY BAND

OFF

15

5

OFF or 1 to 15 time bands

ZSI GF SLOPE

0

3

O

0 to 3

Neutral Protection

NEUTRAL PROT

OFF

150%

OFF

OFF, 50%, 100%, 150%










Protective Relays

PROT RLY ENABLE

ON

OFF

OFF

ON, OFF

VOLTAGE UNBAL PICKUP

10%

50%

10%

10% to 50% steps of 1%

VOLTAGE UNBAL DELAY

OFF

15

1

OFF or 1 to 15 Seconds steps of 1 Second

TRIP ON ZERO V

ON

OFF

OFF

ON, OFF

CURRENT UNBAL PICKUP

10%

50%

10%

10% to 50% steps of 1%

CURRENT UNBAL DELAY

OFF

15

1

OFF or 1 to 15 Seconds steps of 1 Second

UNDER VOLTAGE PICKUP

50%

90%

50%

50% to 90% steps of 1%

UNDER VOLTAGE DELAY

OFF

15

1

OFF or 1 to 15 Seconds steps of 1 Second

OVER VOLTAGE PICKUP

110%

150%

110%

110% to 150% steps of 1%

OVER VOLTAGE DELAY

OFF

15

1

OFF or 1 to 15 Seconds steps of 1 Second

POWER REVERSAL PICKUP

10

990

10

10KW to 990KW steps of 10KW

POWER REVERSAL DELAY

1

15

1

1 to 15 Seconds steps of 1 Second

LOAD ALARM ON

0.55

1.0

.55

0.55 to 1.00 xLT steps of 0.05

LOAD ALARM OFF

0.5

0.95

.5

0.50 to 0.95 xLT steps of 0.05

Note: OFF must be less than ON value