GE Industrial Solutions Spectra RMS Molded Case User Manual
Page 40
GEH-702 Users Manual
39
Register Address
Variable
Value
Factory Default
Read/Write
302
ZSI Short Time Delay Band
0 - OFF
1 - Band1
2 - Band2
3 - Band3
4 - Band4
5 - Band5
6 - Band6
7 - Band7
8 - Band8
9 - Band9
10 - Band10
11 - Band11
12 - Band12
4
Read/Write
303
ZSI Short Time Kst
0 - 0
1 - 2
2 - 8
3 - 18
0
Read/Write
304
ZSI GF Trip Delay
0 - Off
1 - Band1
2 - Band2
3 - Band3
4 - Band4
5 - Band5
6 - Band6
7 - Band7
8 - Band8
9 - Band9
10 - Band10
11 - Band11
12 - Band12
13 - Band13
14 - Band14
15 - Band 15
0
Read/Write
305
ZSI GF Trip K Value
0 - 0
1 - I2T 2
2 - I2T 3
3 - I4T 18
0
Read/Write
312
Reduced Instantaneous Let
Through (RELT)
0 - OFF
1 - ON
0