Register Address
Variable
Value
Factory Default
Read/Write
245
Under Voltage Action
0 - Alarm
1 - Trip
2 - Both
0
Read/Write
246
Over Voltage Action
0 - Alarm
1 - Trip
2 - Both
0
Read/Write
247
Power reversal Action
0 - Alarm
1 - Trip
2 - Both
0
Read/Write
258
Over Voltage Pickup
1 - 110
2 - 111
3 - 112
---- [Increments by 1]
40 - 149
41 - 150
1
Read/Write
259
Over Voltage Delay
0 - Off
1 - 1
2 - 2
3 - 3
4 - 4
5 - 5
6 - 6
7 - 7
8 - 8
9 - 9
10 - 10
11 - 11
12 - 12
13 - 13
14 - 14
15 - 15
0
Read/Write
260
Under Voltage Pickup
1 - 50
2 - 51
---- [Increments by 1]
40 - 89
41 - 90
1
Read/Write
261
Under Voltage Delay
0 - Off
1 - 1
2 - 2
3 - 3
4 - 4
5 - 5
6 - 6
7 - 7
8 - 8
9 - 9
10 - 10 11- 11
12 - 12 13 - 13 14 - 14 15 -15
0
Read/Write
262
Under Voltage Zero-Volt Trip
Enable
0 - Disable
1 - Enable
0
Read/Write