GEH-702 Users Manual

35



Register Address

Variable

Value

Factory Default

Read/Write

245

Under Voltage Action

0 - Alarm

1 - Trip

2 - Both

0

Read/Write

246

Over Voltage Action

0 - Alarm

1 - Trip

2 - Both

0

Read/Write

247

Power reversal Action

0 - Alarm

1 - Trip

2 - Both

0

Read/Write


258


Over Voltage Pickup

1 - 110

2 - 111

3 - 112

---- [Increments by 1]

40 - 149

41 - 150


1


Read/Write







259







Over Voltage Delay

0 - Off

1 - 1

2 - 2

3 - 3

4 - 4

5 - 5

6 - 6

7 - 7

8 - 8

9 - 9

10 - 10

11 - 11

12 - 12

13 - 13

14 - 14

15 - 15







0







Read/Write


260


Under Voltage Pickup

1 - 50

2 - 51

---- [Increments by 1]

40 - 89

41 - 90


1


Read/Write

261

Under Voltage Delay

0 - Off

1 - 1

2 - 2

3 - 3

4 - 4

5 - 5

6 - 6

7 - 7

8 - 8

9 - 9

10 - 10 11- 11

12 - 12 13 - 13 14 - 14 15 -15

0

Read/Write

262

Under Voltage Zero-Volt Trip

Enable

0 - Disable

1 - Enable

0

Read/Write