GEH-702 Users Manual


Table 28. Communication Parameters: Modbus Function 4

Register

Parameter Name

Allowable Values

Read/Write

14

Power Peak Demand Total - Lo 16 bits

32 bit

Read

15

Power Peak Demand Total - Hi 16 bits

Read

18

Voltage Phase A

16 bit

Read

19

Voltage Phase B

16 bit

Read

20

Voltage Phase C

16 bit

Read

21

Current Phase A

16 bit

Read

23

Current Phase B

16 bit

Read

25

Current Phase C

16 bit

Read

27

Current Phase N

16 bit

Read







29







Rating Plug Value

0

60

80

100

125

150

200

225

250

300

350

400

450

500

600

700

750

800

900

1000

1100

1200









Read

31

Energy Total ( 0-15 bits )

16 bit

Read

32

Energy Total (16-31 bits)

16 bit

Read

35

Energy Rollover Count

16 bit

Read

36

Power Factor Phase A

16 bit

Read

37

Power Factor Phase B

16 bit

Read

38

Power Factor Phase C

16 bit

Read

39

Power Factor Total

16 bit

Read

40

Power Real Phase A - Lo 16 bits

32 bit

Read

41

Power Real Phase A - Hi 16 bits

Read

42

Power Real Phase B - Lo 16 bits

32 bit

Read

43

Power Real Phase B - Hi 16 bits

Read

44

Power Real Phase C - Lo 16 bits

32 bit

Read

45

Power Real Phase C - Hi 16 bits

Read

46

Power Real Phase Total - Lo 16 bits

32 bit

Read

47

Power Real Phase Total - Hi 16 bits

Read

48

Power Reactive Phase A - Lo 16 bits

32 bit

Read

49

Power Reactive Phase A - Hi 16 bits

Read

50

Power Reactive Phase B - Lo 16 bits

32 bit

Read