GE Industrial Solutions AF-60 LP Micro Drive Operating Instructions User Manual

Page 30

Advertising
background image

5.2.4 Address Field

The address field of a message frame contains 1 byte. Valid slave device addresses are in the range of 0 - 247 decimal. The individual slave devices are assigned
addresses in the range of 1 - 247 (0 is reserved for broadcast mode, which all slaves recognise). A master addresses a slave by placing the slave address in the
address field of the message.

When the slave sends its response, it places its own address in this address field to let the master know which slave is responding.

5.2.5 Function Field

The function field of a message frame contains 1 byte. Function fields are used to send messages between master and slave. When a message is sent from a
master to a slave device, the function code field tells the slave what kind of action to perform. When the slave responds to the master, it uses the function code
field to indicate either a normal (error-free) response, or that some kind of error occurred (called an exception response).

For a normal response, the slave simply echoes the original function code. For an exception response, the slave returns a code that is equivalent to the original
code with its most significant bit set to logic 1. In addition, the slave places a unique code into the data field of the response message. This tells the master what
kind of error occurred, or the reason for the exception. Please also refer to the sections Function Codes Supported by Modbus RTU and Exception Codes.

5.2.6 Data Field

The data field is constructed using sets of two hexidecimal digits in the range of 00 to FF hexidecimal. These are made up of one RTU character. The data field of
messages sent from a master to a slave device contains additional information which the slave must use to take the action defined by the function code. This
can include items such as addresses of coils or registers, the quantity of items to be handled. and the count of actual data bytes in the field.

5.2.7 CRC Check Field

Messages include an error-checking field, operating on the basis of a Cyclical Redundancy Check (CRC) method. The CRC field checks the content of the entire
message. It is applied regardless of any parity check method used for the individual characters of the message.

The CRC value is calculated by the transmitting device, which appends the CRC as the last field in the message. The receiving device recalculates a CRC during
receipt of the message and compares the calculated value to the actual value received in the CRC field. If the two values are unequal, a bus time-out occurs. The
error-checking field contains a 16-bit binary value implemented as two 8-bit bytes. When this is done, the low-order byte of the field is appended first, followed
by the high-order byte. The CRC high-order byte is the last byte sent in the message.

5.2.8 Coil/Register Addressing

In Modbus, all data are organised in coils and holding registers. Coils hold a single bit, whereas holding registers hold a 2-byte word (i.e. 16 bits). All data addresses
in Modbus messages are referenced to zero. The first occurrence of a data item is addressed as item number zero.

Example:
The coil known as “coil 1” in programmable controller is addressed as coil 0000 in the data address field of a Modbus message. Coil 127 decimal is addressed as
coil 007E

HEX

(126 decimal).

Holding register 40001 is addressed as register 0000 in the data address field of the message. The function code field already specifies a “holding register”
operation. Therefore, the “4XXXX” reference is implicit. Holding register 40108 is addressed as register 006B

HEX

(107 decimal).

AF-60 LP™ Micro Drive Operating Instructions

DET-579A

29

5

Advertising