3 how to control the frequency converter, Af-60 lp™ micro drive operating instructions, 1 function codes supported by modbus rtu – GE Industrial Solutions AF-60 LP Micro Drive Operating Instructions User Manual

Page 32: 2 exception and error codes

Advertising
background image

5.3 How to Control the frequency converter

This section describes codes which can be used in the function and data fields of a Modbus RTU message. For a complete description of all the message fields
please refer to the section Modbus RTU Message Framing Structure.

5.3.1 Function Codes Supported by Modbus RTU

Modbus RTU supports use of the following function codes in the function field of a message:

Function

Function Code

Read coils

1 hex

Read holding registers

3 hex

Write single coil

5 hex

Write single register

6 hex

Write multiple coils

F hex

Write multiple registers

10 hex

Get comm. event counter

B hex

Report slave ID

11 hex

Function

Function code

Sub-function code

Sub-function

Diagnostics

8

1

Restart communication

2

Return

diagnostic

register

10

Clear counters and diagnostic register

11

Return bus message count

12

Return bus communication error count

13

Return bus exception error count

14

Return slave message count

5.3.2 Exception and Error Codes

In the event of an error, the following exception codes may appear in the data field of a response message. For a full explanation of the structure of an exception
(i.e. error) response, please refer to Function Field in section Modbus RTU Message Framing Structure.

MODBUS Exception Codes

Code Name

Meaning

1

Illegal function

The function code received in the query is not an allowable action for the server (or slave). This may be because the function
code is only applicable to newer devices, and was not implemented in the unit selected. It could also indicate that the server (or
slave) is in the wrong state to process a request of this type, for example it is not configured and is being asked to return register
values.

2

Illegal data address The data address received in the query is not an allowable address for the server (or slave). More specifically, the combination

of reference number and transfer length is invalid. For a controller with 100 registers, a register with offset 96 and length 4 would
succeed, a request with offset 96 and length 5 will generate exception 02.

3

Illegal data value

A value contained in the query data field is not an allowable value for server (or slave). This indicates a fault in the structure of
the remainder of a complex request, such as an incorrect implied length. It specifically does NOT mean that a data item submitted
for storage in a register has a value outside the expectation of the application program, since the MODBUS protocol is unaware
of the significance of any particular value of any particular register.

4

Slave device failure An unrecoverable error occurred while the server (or slave) was attempting to perform the requested action

In case of an exception code 4 while accessing parameter values in the drive, detailed information about the latest exception can be read from the drives Holding
Register 0007. This register may contain one of the following, detailed error codes regarding the latest occurring MODBUS Exception.

AF-60 LP™ Micro Drive Operating Instructions

DET-579A

31