6.2.1 Conversion Index

The various attributes of each parameter are displayed in the section Factory Settings. Parameter values are transferred as whole numbers only. Conversion
factors are therefore used to transfer decimals according to the table below.

Example:
Par. 1-24 Motor Current has a conversion index of -2 (i.e. conversion factor of 0.01 according to the table below). To set the parameter to 2.25 A, transfer the value
225 via Modbus. The Conversion Factor of 0.01 means that the value transferred is multiplied by 0.01 in the drive. The vale 225 transferred on the bus is thus
perceived as 2.25 A in the drive.

Conversion index

Conversion factor

2

10

1

100

0

1

-1

0.1

-2

0.01

-3

0.001

-4

0.0001

-5

0.00001

Table 6.1: Conversion table

6.2.2 Change during operation

“TRUE” means that the parameter can be changed while the frequency converter is in operation and “FALSE” means that the frequency converter must be stopped
before a change can be made.

6.2.3 2-Set-up

“All set-up”: The parameter can be set individually in each of the two set-ups, i.e. one single parameter can have two different data values.
”1 set-up”: Data value will be the same in both set-ups.

6.2.4 Type

Data Type

Description

Type

2

Integer 8

Int8

3

Integer 16

Int16

4

Integer 32

Int32

5

Unsigned 8

Uint8

6

Unsigned 16

Uint16

7

Unsigned 32

Uint32

9

Visible string

VisibleString

AF-60 LP™ Micro Drive Operating Instructions

48

DET-579A