Coil number

Description

Signal direction

1 - 16

Frequency converter control word (see table below)

Master to slave

17 - 32

Frequency converter speed or set-point reference
Range 0x0 - 0xFFFF (-200% ... ~ 200%)

Master to slave

33 - 48

Frequency converter status word (see table below)

Slave to master

49 - 64

Open loop mode: Frequency converter output fre-
quency
Closed loop mode: Frequency converter feedback sig-
nal

Slave to master

65

Parameter write control (master to slave)
0 = Parameter changes are written to the RAM of the
frequency converter
1 = Parameter changes are written to the RAM and
EEPROM of the frequency converter

Master to slave

66 - 65536

Reserved

Coil

0

1

01

Preset reference LSB

02

Preset reference MSB

03

DC brake

No DC brake

04

Coast stop

No coast stop

05

Quick stop

No quick stop

06

Freeze outp

No freeze outp

07

Ramp stop

Start

08

No function

Reset

09

No jog

Jog

10

Ramp 1

Ramp 2

11

Data not valid

Data valid

12

Relay 1 off

Relay 1 on

13

Not used

Not used

14

Setup 1

Setup 2

15

Not used

Not used

16

No reversing

Reversing

Frequency converter control word (GE Drive profile)

Coil

0

1

33

Control not ready

Control ready

34

Unit not ready

Unit ready

35

Coasted

Not coasted

36

Error,

tripped

37

Error, no trip

38

Not used

Not used

39

Error, trip locked

40

No warning

Warning

41

Not on reference

On reference

42

Hand mode

Auto mode

43

Out of freq. range

In frequency range

44

Not running

Running

45

No res. brake fault

Resistor brake fault

46

No voltage warning

Voltage warning

47

Not in current limit

Current limit

48

No thermal warning

Thermal warning

Frequency converter status word (GE Drive profile)

Register number

Description

00001 – 00006

Reserved

00007

Last error code. See sectionException and Error Codes.

00008

Reserved

00009

Parameter index*

00100 – 00999

000 parameter group (parameters 001 through 099)

01000 – 01999

100 parameter group (parameters 100 through 199)

02000 – 02999

200 parameter group (parameters 200 through 299)

03000 – 03999

300 parameter group (parameters 300 through 399)

04000 – 04999

400 parameter group (parameters 400 through 499)

49000 – 49999

4900 parameter group (parameters 4900 through 4999)

50000

Input data: Frequency converter control word register (CTW).

50010

Input data: Bus reference register (REF).

50200

Output data: Frequency converter status word register (STW).

50210

Output data: Frequency converter main actual value register (MAV).

Table 5.2: Holding Registers

* Used to specify the index number to be used when accessing an indexed parameter

AF-60 LP™ Micro Drive Operating Instructions