Af-60 lp™ micro drive operating instructions – GE Industrial Solutions AF-60 LP Micro Drive Operating Instructions User Manual

Page 62

Advertising
background image

Normal overload 150% for 1 minute
Frequency converter
Typical Shaft Output [kW]

5.5

7.5

11

15

18.5

22

Typical Shaft Output [HP]

7.5

10

15

20

25

30

IP 20

Unit Size

M3

Unit Size

M3

Output current

Continuous (3 x 380-440 V) [A]

12.0

15.5

23.0

31.0

37.0

43.0

Intermittent (3 x 380-440 V) [A]

18.0

23.5

34.5

46.5

55.5

64.5

Continuous (3 x 440-480 V) [A]

11.0

14.0

21.0

27.0

34.0

40.0

Intermittent (3 x 440-480 V) [A]

16.5

21.3

31.5

40.5

51.0

60.0

Max. cable size:
(mains, motor) [mm

2

/ AWG]

4/10

16/6

Max. input current

Continuous (3 x 380-440 V ) [A]

19.2

24.8

33.0

42.0

34.7

41.2

Intermittent (3 x 380-440 V ) [A]

27.4

36.3

47.5

60.0

49.0

57.6

Continuous (3 x 440-480 V ) [A]

16.6

21.4

29.0

36.0

31.5

37.5

Intermittent (3 x 440-480 V ) [A]

23.6

30.1

41.0

52.0

44.0

53.0

Max. mains fuses [A]

See Section Fuses

Environment
Estimated power loss [W], Best case/
Typical

1)

131.0/

166.8

175.0/

217.5

290.0/

342.0

387.0/

454.0

395.0/

428.0

467.0/

520.0

Weight enclosure IP20 [kg]

3.0

3.0

Efficiency [%], Best case/
Typical

1)

98.0/

97.5

98.0/

97.5

97.8/

97.4

97.7/

97.4

98.1/

98.0

98.1/

97.9

Table 8.4: Mains supply 3 x 380 - 480 VAC

1.

At rated load conditions.

AF-60 LP™ Micro Drive Operating Instructions

DET-579A

61

8

Advertising