Af-60 lp™ micro drive operating instructions – GE Industrial Solutions AF-60 LP Micro Drive Operating Instructions User Manual
Page 62
Normal overload 150% for 1 minute
Frequency converter
Typical Shaft Output [kW]
5.5
7.5
11
15
18.5
22
Typical Shaft Output [HP]
7.5
10
15
20
25
30
IP 20
Unit Size
M3
Unit Size
M3
Output current
Continuous (3 x 380-440 V) [A]
12.0
15.5
23.0
31.0
37.0
43.0
Intermittent (3 x 380-440 V) [A]
18.0
23.5
34.5
46.5
55.5
64.5
Continuous (3 x 440-480 V) [A]
11.0
14.0
21.0
27.0
34.0
40.0
Intermittent (3 x 440-480 V) [A]
16.5
21.3
31.5
40.5
51.0
60.0
Max. cable size:
(mains, motor) [mm
2
/ AWG]
4/10
16/6
Max. input current
Continuous (3 x 380-440 V ) [A]
19.2
24.8
33.0
42.0
34.7
41.2
Intermittent (3 x 380-440 V ) [A]
27.4
36.3
47.5
60.0
49.0
57.6
Continuous (3 x 440-480 V ) [A]
16.6
21.4
29.0
36.0
31.5
37.5
Intermittent (3 x 440-480 V ) [A]
23.6
30.1
41.0
52.0
44.0
53.0
Max. mains fuses [A]
See Section Fuses
Environment
Estimated power loss [W], Best case/
Typical
1)
131.0/
166.8
175.0/
217.5
290.0/
342.0
387.0/
454.0
395.0/
428.0
467.0/
520.0
Weight enclosure IP20 [kg]
3.0
3.0
Efficiency [%], Best case/
Typical
1)
98.0/
97.5
98.0/
97.5
97.8/
97.4
97.7/
97.4
98.1/
98.0
98.1/
97.9
Table 8.4: Mains supply 3 x 380 - 480 VAC
1.
At rated load conditions.
AF-60 LP™ Micro Drive Operating Instructions
DET-579A
61