8.2 Other Specifications

Protection and Features:

Electronic thermal motor protection against overload.

Temperature monitoring of the heatsink ensures that the frequency converter trips in case of overtemperature

The frequency converter is protected against short-circuits on motor terminals U, V, W.

If a motor phase is missing, the frequency trips and issues an alarm.

If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).

Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit voltage is too low or too high.

The frequency converter is protected against earth faults on motor terminals U, V, W.

Mains supply (L1/L, L2, L3/N):

Supply voltage

200-240 V ±10%

Supply voltage

380-480 V ±10%

Supply frequency

50/60 Hz

Max. imbalance temporary between mains phases

3.0 % of rated supply voltage

True Power Factor (λ)

≥ 0.4 nominal at rated load

Displacement Power Factor (cosφ) near unity

(> 0.98)

Switching on input supply L1/L, L2, L3/N (power-ups)

maximum 2 times/min.

Environment according to EN60664-1

overvoltage category III/pollution degree 2

The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 240/480 V maximum.

Motor output (U, V, W):

Output voltage

0 - 100% of supply voltage

Output frequency

0-200 Hz (Advanced Vector Control), 0-400 Hz (u/f)

Switching on output

Unlimited

Ramp times

0.05 - 3600 sec.

Cable lengths and cross sections:

Max. motor cable length, screened/armoured (EMC correct installation)

15 m

Max. motor cable length, unscreened/unarmoured

50 m

Max. cross section to motor, mains*
Connection to load sharing/brake (M1, M2, M3)

6.3 mm insulated Faston Plugs

Max. cross section to load sharing/brake (M4, M5)

16 mm

2

/6AWG

Maximum cross section to control terminals, rigid wire

1.5 mm

2

/16 AWG (2 x 0.75 mm

2

)

Maximum cross section to control terminals, flexible cable

1 mm

2

/18 AWG

Maximum cross section to control terminals, cable with enclosed core

0.5 mm

2

/20 AWG

Minimum cross section to control terminals

0.25 mm

2

* See tables for mains supply for more information!

Digital inputs (Pulse/enocder inputs):

Programmable digital inputs (Pulse/encoder)

5 (1)

Terminal number

18, 19, 27, 29, 33,

Logic

PNP or NPN

Voltage level

0 - 24 V DC

Voltage level, logic'0' PNP

< 5 V DC

Voltage level, logic'1' PNP

> 10 V DC

Voltage level, logic '0' NPN

> 19 V DC

Voltage level, logic '1' NPN

< 14 V DC

Maximum voltage on input

28 V DC

Input resistance, R

i

approx. 4 k

Max. pulse frequency at terminal 33

5000 Hz

Min. pulse frequency at terminal 33

20 Hz

AF-60 LP™ Micro Drive Operating Instructions

62

DET-579A