Response
The normal response is an echo of the query, returned after the register contents have been passed.

Field Name

Example (HEX)

Slave address

01

Function

06

Starting Address HI

00

Starting Address LO

1D

No. of Points HI

00

No. of Points LO

01

Error Check (CRC)

-

Table 5.6: Normal response frame

5.5.6 Preset Multiple Registers (10

HEX

)

Description
This function presets a value into a sequence of holding registers.

Query
The query message specifies the register references to be preset. Register addresses start at zero, i.e. register 1 is addressed as 0.

Example

Write 65535 (655.35s) to PNU734 (4-bytes) mapped to 0 x 1CAB

Field Name

Example (HEX)

Slave address

01

Function

10

Starting Address HI

1C

Starting Address LO

AB

No. of Registers HI

00

No. of Registers LO

02

Byte count

04

Write Data HI (Register 7339)

00

Write Data LO (Register 7339)

00

Write Data HI (Register 7340)

FF

Write Data LO (Register 7340)

FF

Error Check (CRC)

-

Table 5.7: Request frame

Response
The normal response returns the slave address, function code, starting address, and quantity of registers preset.

Field Name

Example (HEX)

Slave address

01

Function

10

Starting Address HI

1C

Starting Address LO

AB

No. of Registers HI

00

No. of Registers LO

02

Error Check (CRC)

-

Table 5.8: Normal response frame

AF-60 LP™ Micro Drive Operating Instructions

36

DET-579A

5