Error code in holding register 0007

Description

00

The parameter number does not exist

01

There is no write access to the parameter

02

The data value exceeds the parameter limits

03

The sub-index in use does not exist

05

The data type does not match the parameter called

17

Data change in the parameter called is not possible in the present mode

18

Other error

130

There is no bus access to the parameter called

5.4 How to Access Parameters

5.4.1 Parameter Handling

The PNU (Parameter Number) is translated from the register address contained in the Modbus read or write message. The parameter number is translated to
Modbus register address as (10 x parameter number -1)

DECIMAL

.

5.4.2 Storage of Data

The Coil 65 decimal determines whether data written to the frequency converter are stored in EEPROM and RAM (coil 65 = 1) or only in RAM (coil 65 = 0).

5.4.3 IND

The array index is set in Holding Register 9 and used when accessing array parameters.

5.4.4 Text Blocks

Parameters stored as text strings are accessed in the same way as the other parameters. The maximum text block size is 20 characters. If a read request for a
parameters is for more characters than the parameter stores, the response is truncated. If the read request for a parameter is for fewer characters than the
parameter stores, the response is space filled.

5.4.5 Conversion Factor

The different attributes for each parameter can be seen in the section on factory settings. Since a parameter value can only be transferred as a whole number,
a conversion factor must be used to transfer decimals. Please refer to the section Conversion Index.

5.4.6 Parameter Values

Standard Data Type
Standard data types are int16, int32, uint8, uint16 and uint32. They are stored as 4x registers (40001 - 4FFFF). The parameters are read using function 03

HEX

“Read

Holding Registers”. Parameters are writtein using the function 6

HEX

“Preset Single Register” for 1 register (16 bits), and the function 10

HEX

“Preset Multiple Registers”

for 2 registers (32 bits). Readable sizes range from 1 register (16 bits) up to 10 registers (20 characters).

Non Standard Data Types
Non standard data types are text strings and are stored as 4x registers (40001 - 4FFFF). The parameters are read using function 03

HEX

“Read Holding Registers”

and written using function 10

HEX

“Preset Multiple Registers”. Readable sizes range from 1 register (2 characters) up to 10 registers (20 characters).

AF-60 LP™ Micro Drive Operating Instructions

32

DET-579A