Af-60 lp™ micro drive operating instructions, 3 force/write multiple coils (0f, 4 read holding registers (03 – GE Industrial Solutions AF-60 LP Micro Drive Operating Instructions User Manual

Page 35

Advertising
background image

Response
The normal response is an echo of the query, returned after the coil state has been forced.

Field Name

Example (HEX)

Slave address

01

Function

05

Coil Address HI

00

Coil Address LO

40

Data HI

FF

Data LO

00

Error Check (CRC)

-

5.5.3 Force/Write Multiple Coils (0F

HEX

)

Description
This function forces each coil in a sequence of coils to either ON or OFF. When broadcast the function forces the same coil references in all attached slaves.

Query
The query message specifies the coils 17 to 32 (speed set-point) to be forced. Coil addresses start at zero, i.e. coil 17 is addressed as 16.

Field Name

Example (HEX)

Slave address

01 (frequency converter address)

Function

0F (write multiple coil)

Coil Address HI

00

Coil Address LO

10 (coil address 17)

Quantity of coils HI

00

Quantity of coils LO

10 (16 coils)

Byte count

02

Force Data HI (coils 8-1)

20

Force Data LO (coils 10-9)

00 (ref. = 2000hex)

Error Check (CRC)

-

Response
The normal response returns the slave address, function code, starting address, and quantity of coils forced.

Field Name

Example (HEX)

Slave address

01 (frequency converter address)

Function

0F (write multiple coils)

Coil Address HI

00

Coil Address LO

10 (coil address 17)

Quantity of coils HI

00

Quantity of coils LO

10 (16 coils)

Error Check (CRC)

-

5.5.4 Read Holding Registers (03

HEX

)

Description
This function reads the content of holding registers in the slave.

Query
The query message specifies the starting register and quantity to be read. Register addresses start at zero, i.e. registers 1-4 are addressed as 0-3.

AF-60 LP™ Micro Drive Operating Instructions