6.2.11 6-** Analog In/Out

Parameter
Number

Parameter Description

Default Value

2 Setup

Change During
Operation

Conver-

sion

Index

Type

6 - 00

Live Zero Timeout Time

10 s

All set-ups

TRUE

0

Uint8

6 - 01

Live Zero TimeoutFunction

[0] Off

All set-ups

TRUE

-

Uint8

6 - 10

Terminal 53 Low Voltage

0.07 V

All set-ups

TRUE

-2

Uint16

6 - 11

Terminal 53 High Voltage

10 V

All set-ups

TRUE

-2

Uint16

6 - 12

Terminal 53 Low Current

0.14 mA

All set-ups

TRUE

-2

Uint16

6 - 13

Terminal 53 High Current

20 mA

All set-ups

TRUE

-2

Uint16

6 - 14

Terminal 53 Low Ref./Feedb. Value

0

All set-ups

TRUE

-3

Int32

6 - 15

Terminal 53 High Ref./Feedb. Value

50

All set-ups

TRUE

-3

Int32

6 - 16

Terminal 53 Filter Time Constant

0.01 s

All set-ups

TRUE

-2

Uint16

6 - 19

Terminal 53 mode

[0] Voltage mode

1 set-up

TRUE

-

Uint8

6 - 22

Terminal 60 Low Current

0.14 mA

All set-ups

TRUE

-2

Uint16

6 - 23

Terminal 60 High Current

20 mA

All set-ups

TRUE

-2

Uint16

6 - 24

Terminal 60 Low Ref./Feedb. Value

0

All set-ups

TRUE

-3

Int32

6 - 25

Terminal 60 High Ref./Feedb. Value

50

All set-ups

TRUE

-3

Int32

6 - 26

Terminal 60 Filter Time Constant

0.01 s

All set-ups

TRUE

-2

Uint16

6 - 81

Keypad potentiometer Low Ref.

0

All set-ups

TRUE

-3

Int32

6 - 82

Keypad potentiometer High Ref.

50

All set-ups

TRUE

-3

Int32

6 - 90

Terminal 42 Mode

[0] 0-20 mA

All set-ups

TRUE

-

Uint8

6 - 91

Terminal 42 Analog Output

[0] No operation

All set-ups

TRUE

-

Uint8

6 - 92

Terminal 42 Digital Output

[0] No operation

All set-ups

TRUE

-

Uint8

6 - 93

Terminal 42 Output Min Scale

0%

All set-ups

TRUE

-2

Uint16

6 - 94

Terminal 42 Output Max Scale

100%

All set-ups

TRUE

-2

Uint16

6.2.12 7-** Controllers

Parameter
Number

Parameter Description

Default Value

2 Setup

Change During
Operation

Conver-

sion

Index

Type

7 - 20

Process CL Feedback 1 Resource

[0] No function

All set-ups

TRUE

-

Uint8

7 - 30

Process PI Normal/ Inverse Control

[0] Normal

All set-ups

TRUE

-

Uint8

7 - 31

Process PI Anti Windup

[1] Enabled

All set-ups

TRUE

-

Uint8

7 - 32

Process PI Start Speed

0 Hz

All set-ups

TRUE

-1

Uint16

7 - 33

Process PI Proportional Gain

0.01

All set-ups

TRUE

-2

Uint16

7 - 34

Process PI Integral Time

9999 s

All set-ups

TRUE

-2

Uint32

7 - 38

Process PI Feed Forward Factor

0%

All set-ups

TRUE

0

Uint16

7 - 39

On Reference Bandwidth

5%

All set-ups

TRUE

0

Uint8

6.2.13 8-** Comm. and Options

Parameter
Number

Parameter Description

Default Value

2 Setup

Change During
Operation

Conver-

sion

Index

Type

8 - 01

Control Site

[0] Digital and ctrl.word

All set-ups

TRUE

-

Uint8

8 - 02

Control Word Source

[1] GE Drive RS485

All set-ups

TRUE

-

Uint8

8 - 03

Control Word Timeout Time

1 s

1 set-up

TRUE

-1

Uint16

8 - 04

Control Word Timeout Function

[0] Off

1 set-up

TRUE

-

Uint8

8 - 06

Reset Control Word Timeout

[0] No function

1 set-up

TRUE

-

Uint8

8 - 30

Protocol

[0] GE Drive

1 set-up

TRUE

0

Uint8

8 - 31

Address

1

1 set-up

TRUE

0

Uint8

8 - 32

GE Drive Port Baud Rate

[2] 9600 Baud

1 set-up

TRUE

-

Uint8

8 - 33

GE Drive Port Parity

[0] Even Parity 1 Stop Bit

1 set-up

TRUE

-

Uint8

8 - 35

Minimum Response Delay

0.01 s

1 set-up

TRUE

-3

Uint16

8 - 36

Max Response Delay

5 s

1 set-up

TRUE

-3

Uint16

8 - 50

Coasting Select

[3] Logic OR

All set-ups

TRUE

-

Uint8

8 - 51

Quick Stop Select

[3] Logic OR

All set-ups

TRUE

-

Uint8

8 - 52

DC Brake Select

[3] Logic OR

All set-ups

TRUE

-

Uint8

8 - 53

Start Select

[3] Logic OR

All set-ups

TRUE

-

Uint8

8 - 54

Reversing Select

[3] Logic OR

All set-ups

TRUE

-

Uint8

8 - 55

Set-up Select

[3] Logic OR

All set-ups

TRUE

-

Uint8

8 - 56

Preset Reference Select

[3] Logic OR

All set-ups

TRUE

-

Uint8

8 - 94

Bus feedback 1

0

All set-ups

TRUE

0

Int16

AF-60 LP™ Micro Drive Operating Instructions

DET-579A

51