2 delivery, 3 storage, 1 storage of the ups – GE Industrial Solutions TLE Series 225-500 Installation Guide User Manual

Page 16: 2 storage of battery, Delivery, Storage, Storage of the ups, Storage of battery

Advertising
background image

Critical Power

Modifications reserved

Page 16/54

GE_UPS_ISG_TLE_SUL_M22_M50_1US_V010.docx

Installation Guide TLE Series 225 - 500 UL S1

4.2 DELIVERY

When delivered, inspect the package integrity and the physical condition of the cabinets carefully.

In case of any damage sustained during transport, immediately inform the carrier and contact your
local Service Center.

A detailed report of the damage is necessary for any insurance claim.

NOTE !

A damaged UPS must never be installed or connected to Utility or Battery!




4.3 STORAGE

4.3.1 Storage of the UPS

The equipment is carefully packed for transport and
storage so that it is in a perfect condition when eventually
installed.

Never leave an UPS outside the building and do not store
the UPS one on top of the other.

We recommend to store the UPS in its original package in
a dry, dust-free room, away from chemical substances,

and with a temperature range not exceeding -13°F (-25°C)
to 131°F (55°C).
In case the battery is included please refer to Section 4.3.2.

Some important functions of the UPS, such as the customized functions, are defined by parameters

stored in a RAM memory.
A small backup Battery located on the Control Unit board supplies the RAM.

If the storage time of the UPS exceeds 1 year, these functions should be verified by an authorized
Service Center before putting the UPS into operation.

4.3.2 Storage of Battery

When the delivery includes a maintenance free Battery, keep in mind that they are subject to self-
discharge and therefore you must recharge the Battery.

The storage time without Battery recharge depends on the temperature of the storage site.

The optimal temperature for Battery storage is 68°F (20°C) to 77°F (25°C) and shall never exceed the
range -4°F (-20°C) to 104°F (40°C).

Recharge stored maintenance free Battery every:
6 months when the storage temperature is 68°F (20°C)
3 months when the storage temperature is 86°F (30°C)
2 months when the storage temperature is 95°F (35°C)

Advertising