5.2 CUSTOMER INTERFACE BOARD

Fig. 5.2-1 Customer Interface Board

J1 connector– RJ45 8P8C (see Section 5.2.1)

Pin 5: TX (out)

Pin 6: RX (in)

Pin 4: GND

X1 terminal block – Output signals on voltage free contacts (see Section 5.2.2)

X1 / 1, 2, 3

NO, C, NC

UTILITY FAILURE

(def. Parameter RL=1)

X1 / 4, 5, 6

NO, C, NC

LOAD ON INVERTER

(def. Parameter RL=3)

X1 / 7, 8, 9

NO, C, NC

STOP OPERATION

(def. Parameter RL=5)

X1 / 12, 13, 14

NO, C, NC

LOAD ON UTILITY

(def. Parameter RL=2)

X1 / 15, 16, 17

NO, C, NC

GENERAL ALARM

(def. Parameter RL=4)

X1 / 18, 19, 20

NO, C, NC

BUZZER (acoustic alarm) (def. Parameter RL=6)

The programmable signals on X1 will be disabled with Q1 open, with the
exception of the signals for “16 - MANUAL BYPASS ON”
and “26 – EMERGENCY
OFF (EPO)”
.

X1 terminal block – Input contacts (see Section 5.2.3)

X1 / 10, 21

NO

Programmable

X1 / 11, 22

NO

Programmable / GENERATOR ON

X2 terminal block –EPO -Emergency Power Off connection (see Section 5.2.4)

X2 / 1, 2

NC

EPO (Emergency Power Off)

Note: to enable this function, remove the Jumper JP2 on “P4 – Customer

Interface” board (see Section 5.2.4).

NO = Normally Open

C = Common

NC = Normally Closed


Output signals on voltage-free contacts

Programmable functions on input contacts

On terminals X1, 6 of the following 27 signals can be selected
from the display, entering with the appropriate password.

Some UPS functions can be activated with
parameters when an external Normally
Open (NO) contact is closed on:

X1/10, 21 or X1/11, 22

Selectable

functions

by

changing

parameters (password required) are:
0 - NO FUNCTION
1 - INVERTER ON
2 - INVERTER OFF
3 – PRINT ALL
4 - STATUS RELAY
5 - GENERATOR ON
6 - EXTERNAL BYPASS
7 - BATTERY FUSES OR EXTERNAL K3

(See Alarm 4104 - Battery Fuses)

8 - eBoost/IEMi CONTROL

Voltage free contacts:
Max. 24Vac / 1A or 60Vdc / 0,5A
IEC-UL-CSA 60950-1 (SELV circuit)
Min. Signal Level: 5Vdc / 5mA

0- NO SIGNAL

1- BUZZER

2- GENERAL ALARM

3- LOAD ON UTILITY

4- STOP OPERATION

5- LOAD ON INVERTER

6- UTILITY FAILURE

7- DC OVERVOLTAGE

8- LOW BATTERY

9- OVERLOAD

10- OVERTEMPERATURE

11- INVERTER-BYPASS NOT SYNCHR.

12- BYPASS LOCKED

13- BYPASS UTILITY FAILURE

14- RECTIFIER UTILITY FAILURE

15- BATTERY DISCHARGE

16- MANUAL BYPASS ON

17- RECTIFIER ON

18- INVERTER ON

19- BOOST CHARGE

20- BATTERY EARTH FAULT

21- BATTERY FAULT

22- RELAY INPUT 1

23- RELAY INPUT 2

24- RELAY OUTPUT ON

25- RELAY OUTPUT OFF

26- EMERGENCY OFF (EPO)

27- eBoost/IEMi MODE