Installation Guide TLE Series 225 - 500 UL S1

4.7.3 Battery over current protection and wire sizing

NOTE !

Please read the safety precautions at the front of this guide carefully, and
thoroughly review the battery manufacturers installation and maintenance
manual before connecting the batteries to the UPS.

The remote rack mounted batteries are to be used then DC over current
protection must be provided by others.

Choose an appropriate DC fuse or circuit breaker using the current data in the
chart below.

Minimum battery cable requirement is based on the current data below.

The maximum available fault current from the battery supply is: 20kA.

The minimum breaker voltage rating is 540V

The AC values below are current ratings per phase.

These maximum and nominal ratings should be considered when choosing the appropriate AC

over current protection device.

NEC (National Electric Code) Section 210-20 (A) rules must be applied.

DC current rating is the nominal battery discharge current which the UPS allows.

(See Fig. 4.7.1-1 and 4.7.1.2)

UPS rating

AC Input Rectifier

AC Input Bypass

AC Input

DC Input

F1

F2

F3

F4

Nom.

Max.

Nom.

Max.

TLE Series 225

285 A

310 A

271 A

285 A

310 A

545 A

TLE Series 250

315 A

345 A

301 A

315 A

345 A

605 A

TLE Series 400

504 A

555 A

481 A

504 A

569 A

968 A

TLE Series 500

630 A

690 A

601 A

630 A

690 A

1210 A

Size of Branch Circuit Over Current Protection - All Models: - "CAUTION - To reduce the risk of fire,

only connect UPS to a circuit provided with (see below) maximum amperes branch circuit over

current protection in accordance with the NEC (National Electric Code), NSI / NFPA 70

UPS rating

F1 - AC Input Rectifier F2 -AC Input Bypass

F3 - AC Input

F4 - DC Input

80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated

TLE Series 225

450 A

350 A

350 A

300 A

450 A

350 A

600 A

600 A

TLE Series 250

450 A

350 A

400 A

350 A

450 A

350 A

600 A

600 A

TLE Series 400

700 A

600 A

700 A

500 A

700 A

600 A

1000 A

1000 A

TLE Series 500 1000 A

700 A

800 A

700 A

1000 A

700 A

1200 A

1200 A

WIRING

Wire sizing according to
NEC Section 210-20 (A) Table 310-16
Use 167°F (75°C) copper or aluminum wire

Wiring requirements:
AC INPUT RECTIFIER:

3-Phase, 4 wire plus Ground

AC INPUT BYPASS:

3-Phase, 4 wire plus Ground

AC OUTPUT:

3-Phase, 4 wire plus Ground

DC INPUT:

2 wire (positive and negative) plus Ground

Maximum recommended cable size

UPS rating

Rectifier Input

Bypass Input

DC Input

AC Output

GND

TLE Series 225
TLE Series 250

2 x 600 kcmil

2 x 500 kcmil

2 x 600 kcmil

2 x 500 kcmil

1 x 400 kcmil

TLE Series 400
TLE Series 500

4 x 600 kcmil

4 x 500 kcmil

4 x 750 kcmil

4 x 500 kcmil

2 x 400 kcmil