Installation Guide TLE Series 225 - 500 UL S1

Fig. 4.9.2-2 Bus connection on first and last units

Final units, first and last, of a RPA Parallel System

On the two boards P13/P14 – IM0022 – Bus Interface Board, of the first and last units of a Parallel

System, the switches SW1-1/2/3/4/5/6 MUST BE IN POSITION ON (see Fig. 4.9.2-2).


Fig. 4.9.2-3 Bus connection on intermediate units

Intermediate units of a RPA Parallel System

On the two boards P13/P14 – IM0022 – Bus Interface Board, of the intermediate units of a Parallel
System
, the switches SW1-1/2/3/4/5/6 MUST BE IN POSITION OFF (see Fig. 4.9.2-3).