1 connector j1 – rj45 8p8c, Connector j1 – rj45 8p8c – GE Industrial Solutions TLE Series 225-500 Installation Guide User Manual

Page 51

Advertising
background image

Critical Power

Modifications reserved

Page 51/54

GE_UPS_ISG_TLE_SUL_M22_M50_1US_V010.docx

Installation Guide TLE Series 225 - 500 UL S1

5.2.1 Connector J1 – RJ45 8P8C

Fig. 5.2.1-1 Connector J1 – RJ45 8P8C

Total remote management of the system using
software GE iUPSGuard, GE Data Protection or GE
Service Software
for system protection and
management of the UPS systems.

Fig. 5.2.1-2 RJ45 –RS232 adaptation cable

TLE Series 225 - 500 is supplied with an
adaptation cable for a serial port RS232 /
sub DB9
connection.

Fig. 5.2.1-3 Connector J1 to PC with RJ45 –RS232 adaptation cable

The connector J1 – RJ45 is enabled on all the
units of the Parallel System
.


5.2.2 X1 terminal block - Output signals on voltage-free contacts

The Customer Interface board provides 6 voltage free relay contacts giving some UPS critical alarms
and operation mode.

These signals are available on terminal blocks X1. Max. rating terminals: 1mm

2

.

The meaning of the alarms on the free contacts in standard configuration (default) is the following:

X1 / 1, 2, 3

(NO, C, NC)

UTILITY FAILURE

(def. Parameter RL=1)

X1 / 4, 5, 6

(NO, C, NC)

LOAD ON INVERTER

(def. Parameter RL=3)

X1 / 7, 8, 9

(NO, C, NC)

STOP OPERATION

(def. Parameter RL=5)

X1 / 12, 13, 14

(NO, C, NC)

LOAD ON UTILITY

(def. Parameter RL=2)

X1 / 15, 16, 17

(NO, C, NC)

GENERAL ALARM

(def. Parameter RL=4)

X1 / 18, 19, 20

(NO, C, NC)

BUZZER (ACOUSTIC ALARM)

(def. Parameter RL=6)

In case different alarms or operating status are required, they can be configured on the same terminals
via software from the control panel.

The configuration can be changed in parameters mode by a trained operator using the appropriate
password.

NOTE !

The programmable signals on X1 will be disabled with Q1 open, with the exception of
the signals for “16 - MANUAL BYPASS ON”
and “26 – EMERGENCY ON (EPO)”.


5.2.3 X1 terminal block - Programmable input free contacts

Some programmable UPS functions (indicated in Section 9.2), can be activated by closing an external
contact, if connected, on:

X1 / 10, 21

User Input 1 (default = Not used)

X1 / 11, 22

User Input 2 (default = GENERATOR ON)

J1 - RJ45

SGSE_

400-500_S

3_Custom

er interfa

ce-J1-R

J45_01

20

1 2 3

12 13 14

4

17

15 16

18 19

5 6 7

8 9

21 22

10 11

SNMP card

6

9

1

5

2
3
4

7
8

CNT_Cable RJ45-RS232_01

8

1

J1 - RJ45

J1 - RS232