10 epo command connection (emergency power off), Epo command connection (emergency power off), Ep o ep o – GE Industrial Solutions TLE Series 225-500 Installation Guide User Manual

Page 47: Critical power, 24 vdc for external (uvr) battery breaker

Advertising
background image

Critical Power

Modifications reserved

Page 47/54

GE_UPS_ISG_TLE_SUL_M22_M50_1US_V010.docx

Installation Guide TLE Series 225 - 500 UL S1

4.10 EPO COMMAND CONNECTION (EMERGENCY POWER OFF)

WARNING !

The connection of an emergency button EPO (Emergency Power Off) must be
performed by QUALIFIED SERVICE PERSONNEL only when the UPS is
COMPLETELY POWERED DOWN.

BE AWARE !

The reliability of the system depends on this contact NC (Normally Closed)!

An Emergency button (Normally Closed voltage-free contact) can be connected on terminals XA /
EPO-1, EPO-2
. Max. rating XA terminals: 2.5mm

2

.

Fig. 4.10-1 XA terminal block for EPO command connection

When opened, this contact causes the immediate
opening of the Contactors K6 and K7 as well as
the shut-down of Rectifier, Inverter and Static-
Switch
.

NOTE !

This procedure could imply a
Load
shut-down.

NOTE !

To operationalize this function, in case that the UPS was provided with one or
more cards “P4 - Customer Interface”
, there must be on each card the following:
- Remove the cable short-circuiting terminals X2 / 1, 2
(see Fig. 4.10-2).
- Remove the Jumper JP2
(see Fig. 4.10-2).

Fig. 4.10-2 X2 terminal block and Jumper JP2 on the P4 – Customer Interface Board



When the EPO has been activated, the system must be restored as follows:

Realize the push-button EPO (contact on XA / EPO-1, EPO-2 is closed again).

Press the key Inverter OFF on the Control Panel (see User Manual to Section 6.5).

In case of a Parallel System press the key “O” (Inverter OFF) on the Control Panel of
each unit connected on the Parallel Bus and having its output switch Q1 closed.

SGSE_400-500_S3_Custom

er interface-XA_01

Customer Interface

1

12 13 14 15 16

17 18 19 20

21 22

2 3 4 5 6

7 8 9

10 11

XA

EPO

EPO

+

-

TLES_UL_400-500

_S1_Terminals XA_

01

XA

EP

O

EP

O

+

-

24 Vdc for
External (UVR)
Battery Breaker

X2

10

9

8

21

19 20

22

11

SGSE_

600_S1

_Custom

er interf

ace-X2

EPO_0

1

SNMP card

14

13

12

2

1

7

6

5

16

15

4

3

18

17

X1

X2

J1

JP2

1

2

8

19

21

22

20

10

11

9

17

18

16

15

7

6

5

4

12

14

13

3

2

1

X1

X2

J1

SE_

40

0-

50

0_

S1_C

usto

m

er

interfac

e-JP

2_01

Advertising