4 x2 terminal block - epo (emergency power off), 5 x1 terminal block - gen set signalling (gen on), X2 terminal block - epo (emergency power off) – GE Industrial Solutions TLE Series 225-500 Installation Guide User Manual

Page 52: X1 terminal block - gen set signalling (gen on), Critical power

Advertising
background image

Critical Power

Modifications reserved

Page 52/54

GE_UPS_ISG_TLE_SUL_M22_M50_1US_V010.docx

Installation Guide TLE Series 225 - 500 UL S1

5.2.4 X2 terminal block - EPO (Emergency Power Off)

NOTE !

If an emergency button EPO (Emergency Power Off) is installed, the use of the XA
terminals is recommended (see Section 5.10)
.


Fig. 5.2.4-1 X2 terminals in the P4 – Customer Interface

Fig. 5.2.4-2 Jumper JP2 on the P4 – Customer Interface


NOTE !

To activate the connection of an emergency button EPO (Emergency Power Off) on
the terminals XA / EPO-1, EPO-2,
performed on each card “P4 – Customer Interface”
the following operation:
- Remove the cable short-circuiting terminals X2 / 1, 2
(see Fig. 5.2-4-1).
- Remove the Jumper JP2
(see Fig. 5.2-4-2).





5.2.5 X1 terminal block - Gen Set Signalling (GEN ON)

If an emergency generator set supplies the UPS in case of Utility Failure and the generator is

considerably unstable in frequency, it should be suitable to install the signal GENERATOR ON on X1 /
11, 22
. See Fig. 5.2-1 / X1.

Since the Parameter for of the reading of the Generator function is password protected, call the nearest
Service Center for it's activation.

When this contact closes, it changes certain (programmable) functions such as:

Enabling or disabling of synchronization and consequently the Load transfer to generator.

Reduction or elimination or delay of Battery recharging during the generator operation.

Additionally, when the GENERATOR ON input contact is closed, the UPS will inhibit eBoost™ Operation
Mode
and revert to double-conversion operation.

It is advised to contact your Service Center for further details.

In a Parallel System a separate NO (Normally Open) contact must be connected to
each individual unit.

X2

10

9

8

21

19 20

22

11

SGSE_

600_S1

_Custom

er interf

ace-X2

EPO_0

1

SNMP card

14

13

12

2

1

7

6

5

16

15

4

3

18

17

X1

X2

J1

JP2

1

2

8

19

21

22

20

10

11

9

17

18

16

15

7

6

5

4

12

14

13

3

2

1

X1

X2

J1

SE_

40

0-

50

0_

S1_C

usto

m

er

interfac

e-JP

2_01

Advertising