Installation Guide TLE Series 225 - 500 UL S1

NEC SECTION 210-20 (A)

Table 310-16. Allowable Ampacities of Insulated Conductors Rated O Through 2000 Volts, 140°F Trough
194°F (60°C Trough 90°C) Not More than Three Current-Carrying Conductors in Raceway, Cable, or Earth
(Directly Buried), Based on Ambient Temperature of 86°F (30°C).

Temperature Rating of Conductor (See table 310-13)

Size

140°F (60°C)

167°F (75°C)

194°F (90°C)

140°F (60°C)

167°F (75°C)

194°F (90°C)

AWG

or

kcmil

Types

TW, UF

Types

FEPW, RH, RHW,

THHW, THW,

THWN, XHHW,

USE, ZW

Types

TBS, SA, SIS, FEP,

FEPB, MI, RHH,
RHW-2, THHN,

THHW, THW-2,

THWN-2, USE-2,

XHH, XHHW,

XHHW-2,ZW-2

Types

TW, UF

Types

RH, RHW,

THHW,

THW, THWN,

XHHW, USE

Types

TBS, SA, SIS,

THHN, THHW,

THW-2,

THWN-2, RHH,

RHW-2, USE-2,

XHH, XHHW,

XHHW-2,

ZW-2

COPPER

ALUMINUM or COPPER-CLAD ALUMINUM

18

---

---

14

---

---

---

16

---

---

18

---

---

---

14

20

20

25

---

---

---

12

25

25

30

20

20

25

10

30

35

40

25

30

35

8

40

50

55

30

40

45

6

55

65

75

40

50

60

4

70

85

95

55

65

75

3

85

100

110

65

75

85

2

95

115

130

75

90

100

1

110

130

150

85

100

115

1/0

125

150

170

100

120

135

2/0

145

175

195

115

135

150

3/0

165

200

225

130

155

175

4/0

195

230

260

150

180

205

250

215

255

290

170

205

230

300

240

285

320

190

230

255

350

260

310

350

210

250

280

400

280

335

380

225

270

305

500

320

380

430

260

310

350

600

355

420

475

285

340

385

700

385

460

520

310

375

420

750

400

475

535

320

385

435

800

410

490

555

330

395

450

900

435

520

585

355

425

480

1000

455

545

615

375

445

500

1250

495

590

665

405

485

545

1500

520

625

705

435

520

585

1750

545

650

735

455

545

615

2000

560

665

750

470

560

630

CORRECTION FACTORS

Ambient

Temperature

For ambient temperatures other than 86°F (30°C), multiply the allowable ampacities shown above by the

appropriate factor below

70 – 77°F (21 – 25°C)

1.08

1.05

1.04

1.08

1.05

1.04

79 – 86°F (26 - 30°C)

1.00

1.00

1.00

1.00

1.00

1.00

88 – 95°F (31 - 35°C)

0.91

0.94

0.96

0.91

0.94

0.96

97 – 104°F (36 - 40°C)

0.82

0.88

0.91

0.82

0.88

0.91

106 – 113°F (41 - 45°C)

0.71

0.82

0.87

0.71

0.82

0.87

115 – 122°F (46 - 50°C)

0.58

0.75

0.82

0.58

0.75

0.82

124 – 131°F (51 - 55°C)

0.41

0.67

0.76

0.41

0.67

0.76