Galaxy Power System 4812/24

Issue 9 Januray 2008

Troubleshooting Millennium Systems 13 - 9

Controller

Major

Controller Fail

--

•BSH failure
•BSJ failure
•Option board

failure

•Display failure
•BIC failure

Replace BIC per GPS
Installation Guide Section
16, “Replacing Bay
Interface Card (BIC)”.

Controller

Major

Circuit Pack Fail

--

See “Controller
Fail”.

See “Controller Fail”.

Controller

Major

Controller Fuse

--

Fuse has
operated.

Replace the controller fuse
labeled F2 (intelligent
power).

Controller

Major

Alarm Battery
Supply Fuse

--

Fuse has
operated.

Replace the controller fuse
labeled F5 (alarm battery
supply).

Controller

Major

Remote Peripheral
Fuse

--

Fuse has
operated.

Replace the controller fuse
labeled F1 (option power).

Controller

Major

Sense/Control Fuse --

Fuse has
operated.

Replace the controller fuse
labeled F4 (voltage sense).

Controller

Major

Bay Interface ID
Conflict

--

Two or more bay
interface cards
(BICs) have the
same ID number.

Following instructions
printed on the label over the
BIC, adjust the DIP
switches to change the ID
number.

Controller

Major

Major
Communication
Fail Alarm

Blinking
ALM LED
on rectifiers
or
red LED on
BIC

Loss of
communication
with controller:
•Defective

interface from
BIC or multiple
rectifiers to
controller

•Internal failure

of controller,
BIC, or multiple
rectifiers

1. Verify that the controller

is powered and operating
correctly.

2. If there are no controller

alarms, replace the
equipment that has lost
communication.

•If the problem is not

corrected, call technical
support.

Table 13-C: Controller Alarms

(See Figures 12-2 and 12-3)

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Other

Indication(s)

Possible

Problem(s)

Possible Solution(s)