9 - 4 Specifications

Issue 9 Preoiminary Januray 2008

Output 596D

Output Power

1, 2

6,000W maximum

Output Current

1, 2

110Adc maximum from -40°C to +45°C

85Adc at +60°C

60Adc at +70°C

47.5Adc at +75°C


Rectifier self-derates at approximately

1.5 amperes per degree C (+45°C to +60°C)

2.5 amperes per degree C (+60°C to +75°C)

Float/Boost Voltage

42-58Vdc

Total Harmonic Distortion

<5% at Nominal Vac and >50Adc

Regulation

±0.5%

Ripple

100 mVrms

Noise

< 2mV psophometric

Current Limit Set Point

30A-110A

Mechanical

Width

5.25 in. (133.35 mm)

Height

8 in. (203.2 mm)

Depth

19.75 in. (501.65 mm)

Weight

20 lbs. (9 kg)

Environmental

Efficiency

> 90% typical

Heat Release

596A

52Vdc, 40A
52Vdc, 50A
54.5Vdc, 40A
54.5Vdc, 50A
55Vdc, 55A

596D

52Vdc, 80A
52Vdc, 100A
54.5Vdc, 80A
54.5Vdc, 100A
54.5Vdc, 110A

Per rectifier:
231W [788.9 BTU/hr]
288W [983 BTU/hr]
242W [827 BTU/hr]
302W [1,030 BTU/hr]
332W [1,133 BTU/hr]

463W [1,578 BTU/hr]
577W [1,966 BTU/hr]
485W [1,654 BTU/hr]
605W [2,060 BTU/hr]
666W [2,266 BTU/hr]

Storage Relative Humidity

5% to 90%

Audible Noise

< 52dBA

EMC

EN 50022, level B, conducted and radiated (CISPR 22)

Standards Compliance

Safety Standard

EN 60950 (IEC950)

Certification Marks

UL, VDE, CE
Rectifiers are individually UL Recognized and/or CSA
Certified to UL1950 and CSA C22.2 No 234/950. Rectifiers
are also approved to IEC-950/EN60950 by an EC Notified
Body and have outputs classified as SELV.

1. See Figure 9-1: Output Current vs. Temperature.
2. Output is limited to 3,000W when installed in rectifier shelves designated for 596A only to protect the ac input conductors.

Table 9-B: Rectifier Specifications (Continued)

Advertising