Rectifier

Minor

External Transfer
Shutdown

STBY

TR

System is
operating on
external
engine.

No action required.

Rectifier

Minor

High Float Voltage

None

None

Configuration
problem

Call technical support.

Rectifier

Minor

Excess Rectifier
Drain

None

None

Internal
rectifier fault

Replace rectifier.

Rectifier

Minor

Excess System
Drain

None

None

System load
exceeds shunt
rating.

Call technical support.

Rectifier

Minor

Limited Recharge

None

None

Rectifier
capacity has
been
exceeded.

Install more rectifiers.

Table 13-E: Rectifier Related Alarms