GE Industrial Solutions GPS 4812_24 User Manual
Page 109
Galaxy Power System 4812/24
Issue 9 Januray 2008
Troubleshooting Millennium Systems 13 - 15
Rectifier
Minor
External Transfer
Shutdown
STBY
TR
System is
operating on
external
engine.
No action required.
Rectifier
Minor
High Float Voltage
None
None
Configuration
problem
Call technical support.
Rectifier
Minor
Excess Rectifier
Drain
None
None
Internal
rectifier fault
Replace rectifier.
Rectifier
Minor
Excess System
Drain
None
None
System load
exceeds shunt
rating.
Call technical support.
Rectifier
Minor
Limited Recharge
None
None
Rectifier
capacity has
been
exceeded.
Install more rectifiers.
Table 13-E: Rectifier Related Alarms
(See Figures 12-6 and 12-8)
Controller
LED
Controller
Alarm
Status
Millennium
Controller Display
Rectifier
LED
Rectifier
Display
Possible
Problem(s)
Possible Solution(s)