GE Industrial Solutions GPS 4812_24 User Manual

Page 104

Advertising
background image

Galaxy Power System 4812/24

13 - 10 Troubleshooting Millennium Systems

Issue 9 Januray 2008

Controller

Minor

Minor
Communication
Fail Alarm

Blinking
ALM LED
on rectifier

Loss of
communication
with controller:
•Defective

interface from
rectifier to
controller

•Internal

controller or
rectifier failure

1. Verify that the controller

is powered and operating
correctly.

2. If there are no controller

alarms, replace the
equipment that has lost
communication.

•If the problem is not

corrected, call technical
support.

Controller

Minor

Self Fail Test

--

See “Controller
Fail”.

See “Controller Fail”.

Controller

Minor

Thermal Probe
Failure

--

Battery thermal
probe has failed.

Call technical support.

Table 13-C: Controller Alarms

(See Figures 12-2 and 12-3)

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Other

Indication(s)

Possible

Problem(s)

Possible Solution(s)