Controller alarms, Table 14-c: controller alarms – GE Industrial Solutions GPS 4812_24 User Manual

Page 118

Advertising
background image

Galaxy Power System 4812/24

14 - 6 Troubleshooting Vector Systems

Issue 9 Januray 2008

Controller Alarms

Table 14-C: Controller Alarms

(See Figures 12-4 and 12-5)

Controller

Alarm

Status

Vector

Controller Display

Other

Indication(s)

Possible Problem(s)

Possible Solution(s)

Major

None

--

•Controller failure

Check controller to see if the
green LED is extinguished and
the red LED is lit. If so, perform
the following steps:
1. Remove and reset the

controller circuit board. If all
diagnostics pass, it is possible
that some type of “one time”
abnormality occurred to cause
the failure.

2. If the diagnostics did not pass,

replace the controller circuit
board and verify the failure is
resolved.

3. If the problem is not corrected,

call technical support.

Major

None

--

•Controller failure
•Display failure

If the front panel LED module,
LEDs, or switches fail, perform
the following steps:
1. Verify that the ribbon cable

from the controller board to the
BMW display is not cut,
abraded, or otherwise mangled.
Replace the cable if damaged.

2. Reset the controller board.
3. If the display is still not

operating, replace the display
module.

Minor

TEMP PROBE
FAIL

--

Battery thermal probe
has failed.

Call technical support.