Controller alarms, Table 14-c: controller alarms – GE Industrial Solutions GPS 4812_24 User Manual
Page 118
Galaxy Power System 4812/24
14 - 6 Troubleshooting Vector Systems
Issue 9 Januray 2008
Controller Alarms
Table 14-C: Controller Alarms
(See Figures 12-4 and 12-5)
Controller
Alarm
Status
Vector
Controller Display
Other
Indication(s)
Possible Problem(s)
Possible Solution(s)
Major
None
--
•Controller failure
Check controller to see if the
green LED is extinguished and
the red LED is lit. If so, perform
the following steps:
1. Remove and reset the
controller circuit board. If all
diagnostics pass, it is possible
that some type of “one time”
abnormality occurred to cause
the failure.
2. If the diagnostics did not pass,
replace the controller circuit
board and verify the failure is
resolved.
3. If the problem is not corrected,
call technical support.
Major
None
--
•Controller failure
•Display failure
If the front panel LED module,
LEDs, or switches fail, perform
the following steps:
1. Verify that the ribbon cable
from the controller board to the
BMW display is not cut,
abraded, or otherwise mangled.
Replace the cable if damaged.
2. Reset the controller board.
3. If the display is still not
operating, replace the display
module.
Minor
TEMP PROBE
FAIL
--
Battery thermal probe
has failed.
Call technical support.