Ac system alarm led, Table 13-a: ac alarms – GE Industrial Solutions GPS 4812_24 User Manual

Page 97

Advertising
background image

Galaxy Power System 4812/24

Issue 9 Januray 2008

Troubleshooting Millennium Systems 13 - 3

AC System Alarm

LED

Table 13-A: AC Alarms

(See Figure 12-8)

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Other

Indication(s)

Possible

Problem(s)

Possible Solution(s)

AC

System

Minor

AC Fail

ACF on
rectifier
display

Rectifier is not
receiving ac
power:
•AC input circuit

breaker has
operated.

•AC input

voltage is out of
range.

•Internal rectifier

failure

1. Verify that ac circuit

breaker is closed; close
circuit breaker if
operated.

2. If the problem is not

corrected, replace the
rectifier.

AC

System

Minor

Engine Transfer
Timeout

Engine may
have alarm.

Remote engine
or connection to
engine has
failed.

Call technical support.

AC

System

Minor

Phase Alarm

PF on
rectifier
display

Phase failure:
•Rectifier high

voltage
shutdown

•External phase

imbalance or
failure

•Internal rectifier

failure

1. Toggle the ON/STBY

switch into the STBY
position and then back
into the ON position.

2. If the problem is not

corrected, replace the
rectifier.