Battery on discharge and remote modules alarm leds, Or no led, Table 13-f: miscellaneous alarms – GE Industrial Solutions GPS 4812_24 User Manual

Page 110

Advertising
background image

Galaxy Power System 4812/24

13 - 16 Troubleshooting Millennium Systems

Issue 9 Januray 2008

Battery on

Discharge and

Remote Modules

Alarm LEDs,

or No LED

Table 13-F: Miscellaneous Alarms

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Other

Indication(s)

Possible

Problem(s)

Possible Solution(s)

Battery on

Discharge

Major

Battery on
Discharge

Rectifiers
may say
ACF.

Temporary
condition that
may be
associated with
other alarms

Call technical support.

Remote

Modules

Minor

Module Failure

Green LED
on RPM will
not blink.

Remote
Peripheral
Module has
failed.

Call technical support.

Remote

Modules

Minor

Measurement Out
of Range

--

•Data being

sensed exceeds
remote
peripheral
module’s
capability.

•Remote

peripheral
module has
failed.

Call technical support.

None

Major

Auxiliary Major

Auxiliary
equipment
may have
alarm.

Problem with
operation of
auxiliary
equipment

Call technical support.

None

Minor

Auxiliary Minor

Auxiliary
equipment
may have
alarm.

Problem with
operation of
auxiliary
equipment

Call technical support.

None

None

None

•STBY LED

on rectifier
is lit.

•TR on

rectifier
display

Remote transfer:
•Rectifier is in

STBY.

Remove the remote standby
command issued by the
controller.