GE Industrial Solutions GPS 4812_24 User Manual
Page 64
Table 9-A: Galaxy Power System 4812/24 Specifications (continued)
Mechanical
Cabinet
Full Height
Half Height
Nominal Cabinet Dimensions
(H x W x D)
2100 H x 600 W x 500 D mm
(82.6 H x 23.6 W x 19.7 in.)
1080 H x 600 W x 500 D mm
(42.5 H x 23.6 W x 19.7 D in)
Units Per Initial Cabinet
Full Height
Half Height
Rectifiers
1 - 12 or 1 - 16
1 - 8
Controller
1
Battery Disconnect Modules
0 - 1
DC Distribution
1 - 6
1 - 3
Units Per Supplemental Cabinet
Rectifiers
1 - 12 or 1 - 8
N/A
Battery Disconnect Modules
0 - 1
N/A
DC Distribution
1 - 6
N/A
Environmental
Operating Ambient Temperature
596A2
596D
-40°C to +85°C
-40°C to +75°C
Altitude
-50 to 4000 meters
Note: For altitudes between 1500 and 4000 meters, derate the maximum
temperature by 0.656°C per 100 meters.
Humidity
5% to 90% non-condensing
Radiated and Conducted
Emissions
EN50082-1, EN50082-2, EN50081, EN61000
Electromagnetic Immunity
Level B
Earthquake Rating
Zone 4, upper floors
Standards Compliance
Agency Approvals
CE Marked, UL
Underwriters Laboratories (UL) Listed per Subject Letter 1801, DC Power
Distribution Centers for Telecommunications Equipment
Galaxy Power System 4812/24
9 - 2 Specifications
Issue 9 Preoiminary Januray 2008