GE Industrial Solutions GPS 4812_24 User Manual

Page 64

Advertising
background image

Table 9-A: Galaxy Power System 4812/24 Specifications (continued)

Mechanical

Cabinet

Full Height

Half Height

Nominal Cabinet Dimensions

(H x W x D)

2100 H x 600 W x 500 D mm
(82.6 H x 23.6 W x 19.7 in.)

1080 H x 600 W x 500 D mm
(42.5 H x 23.6 W x 19.7 D in)

Units Per Initial Cabinet

Full Height

Half Height

Rectifiers

1 - 12 or 1 - 16

1 - 8

Controller

1

Battery Disconnect Modules

0 - 1

DC Distribution

1 - 6

1 - 3

Units Per Supplemental Cabinet

Rectifiers

1 - 12 or 1 - 8

N/A

Battery Disconnect Modules

0 - 1

N/A

DC Distribution

1 - 6

N/A

Environmental

Operating Ambient Temperature

596A2
596D

-40°C to +85°C
-40°C to +75°C

Altitude

-50 to 4000 meters

Note: For altitudes between 1500 and 4000 meters, derate the maximum
temperature by 0.656°C per 100 meters.

Humidity

5% to 90% non-condensing

Radiated and Conducted
Emissions

EN50082-1, EN50082-2, EN50081, EN61000

Electromagnetic Immunity

Level B

Earthquake Rating

Zone 4, upper floors

Standards Compliance

Agency Approvals

CE Marked, UL
Underwriters Laboratories (UL) Listed per Subject Letter 1801, DC Power
Distribution Centers for Telecommunications Equipment

Galaxy Power System 4812/24

9 - 2 Specifications