Battery alarms, Table 14-b: battery alarms – GE Industrial Solutions GPS 4812_24 User Manual

Page 117

Advertising
background image

Galaxy Power System 4812/24

Issue 9 Januray 2008

Troubleshooting Vector Systems 14 - 5

Battery Alarms

Table 14-B: Battery Alarms

(See Figure 12-7)

Controller

Alarm

Status

Vector

Controller Display

Other

Indication(s)

Possible Problem(s)

Possible Solution(s)

Major

VERY LOW

VOLTAGE

--

Occurs in an operating
system following an
extended commercial ac
power outage, during
which the batteries are
providing power for the
system and the system
voltage is approaching
the user-defined low
limit.

1. If commercial ac power is

present but the system voltage
remains low, call technical
support.

2. Investigate other alarms that

may be present
(rectifier-related alarms and
the AC Fail alarm may also
occur during the fault
condition).

Major

CONTACTOR1

OPEN

Red LED on
contactor
drive board
is lit.

Contactor is open:
•Open has been initiated

by controller.

•Open has been initiated

manually.

1. Follow instructions on the

label adjacent to the contactor
drive board (see Figure 12-7).

2. If the problem is not corrected,

call technical support.

Major

CONTACTOR1

FAIL

--

Contactor or drive board
has failed.

Call technical support.

Major

HIGH BATT

TEMP

Alarm on
210E unit, if
equipped

Batteries have exceeded
temperature threshold.

Call technical support.