Galaxy Power System 4812/24

Issue 9 Januray 2008

Troubleshooting Millennium Systems 13 - 13

Rectifier

Minor

Rectifier Fail

ALM

TA

Thermal
alarm:
•Excessive

ambient
temperature

•Internal

rectifier
failure

1. Verify that there is

no obstruction of
the fan inlet.

2. Toggle the ON/

STBY switch into
the STBY position
and then back into
the ON position.

3. If the problem is

not corrected,
replace the rectifier.

Rectifier

Minor

Rectifier Fail

ALM

ICS
IP5
IP6
IP7

Internal
rectifier
failure

1. Place the ac circuit

breaker for the
rectifier in the OFF
position.

2. Remove the

rectifier from the
shelf.

3. Wait for 30 seconds

or until all front
panel display LEDs
have extinguished.

4. Replace the

rectifier.

5. Return the ac

breaker to the ON
position.

6. Place the rectifier

ON/STBY switch
into the ON
position.

7. If the problem is

not corrected,
replace the rectifier.

Rectifier

Minor

Rectifier Fail

ALM

FSE

Fuse alarm:
•DC fuse open
•Internal

rectifier
failure

1. Toggle the ON/

STBY switch into
the STBY position
and then back into
the ON position.

2. If the problem is

not corrected,
replace the rectifier.

Table 13-E: Rectifier Related Alarms

(See Figures 12-6 and 12-8)

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Rectifier

LED

Rectifier

Display

Possible

Problem(s)

Possible Solution(s)