Distribution

Major

External Fuse
Major

Alarm LED
on dc
distribution
panel is lit.

DC load fuse or
circuit breaker
has operated.

Replace fuse or reset
circuit breaker.

Distribution*

*Alarm must
be configured
to turn on the
Distribution
LED; not a
factory
default.

Major

Contactor 2 (or 3)
Open

Red LED on
contactor
drive board is
lit.

Contactor is
open:
•Open has been

initiated by
controller.

•Open has been

initiated
manually.

1. Follow instructions on

the label adjacent to the
contactor drive board
(see Figure 12-10).

2. If the problem is not

corrected, call
technical support.

Distribution*

*Alarm must
be configured
to turn on the
Distribution
LED; not a
factory
default.

Major

Contactor 2 (or 3)
Fail

--

Contactor or
drive board has
failed.

Call technical support.