Rectifiers, 596 series a and d, Overview – GE Industrial Solutions GPS 4812_24 User Manual

Page 37: Front panel display, Power switch, Status indicators, 4 rectifiers, Overview 4-1, 4rectifiers

Advertising
background image

Galaxy Power System 4812/24

Issue 9 Januray 2008

Rectifiers 4 - 1

4

Rectifiers

596 Series A and D

Overview

The 596 Series A rectifier (55A) and 596D rectifier (110A) operate from
single-phase ac service with a phase-to-phase voltage within the range
of 176-264Vac.

The rectifiers are shipped separately from the cabinets for quick and
straightforward installation into rectifier shelves at the site.
Interconnections to ac input, dc output, and control signals occur
automatically during insertion. The rectifier is keyed to prevent
installation of the wrong rectifier. No settings or adjustments to
potentiometers are necessary. The installer must set the rectifier’s ID
using the ON/STBY switch to allow the controller to learn the rectifier’s
physical location.

The 596A and D rectifiers are UL Recognized for both the U. S. and
Canada, comply with UL1950 (Information Technology Equipment),
and meet EN60950 requirements.

Front Panel Display

Power Switch

This three-position switch has two active states:

It controls the on/standby state of the rectifier.

It is used to set the rectifier ID.

Status Indicators

In addition to the ON and STBY LEDs, four other LEDs on the
rectifier’s faceplate indicate the rectifier’s condition.

The ALM LED is red and lights whenever the rectifier fails.

Advertising