Galaxy Power System 4812/24

14 - 4 Troubleshooting Vector Systems

Issue 9 Januray 2008

AC Alarms

Table 14-A: AC Alarms

(See Figure 12-8)

Controller

Alarm

Status

Vector

Controller Display

Other

Indication(s)

Possible Problem(s)

Possible Solution(s)

Major

MULTIPLE AC

FAIL

ACF on
rectifier
display

Rectifier(s) not
receiving ac power:
•AC input circuit

breaker has operated.

•AC input voltage is out

of range.

•Internal rectifier failure

1. Verify that ac circuit breaker is

closed; close circuit breaker if
operated.

2. If the problem is not corrected,

replace the rectifier(s).

Minor

ac failure

ACF on
rectifier
display

Rectifier not receiving
ac power:
•AC input circuit

breaker has operated.

•AC input voltage is out

of range.

•Internal rectifier failure

1. Verify that ac circuit breaker is

closed; close circuit breaker if
operated.

2. If the problem is not corrected,

replace the rectifier.

Minor

phase failure

PF on
rectifier
display

Phase failure:
•Rectifier high voltage

shutdown

•External phase

imbalance or failure

•Internal rectifier failure

1. Toggle the ON/STBY switch

into the STBY position and
then back into the ON position.

2. If the problem is not corrected,

replace the rectifier.