Galaxy Power System 4812/24

Issue 9 Januray 2008

Troubleshooting Vector Systems 14 - 9

Minor

RECTIFIER FAIL

ALM

HO

High output
voltage:
•Rectifier high

voltage
shutdown

•Internal

rectifier failure

1. Verify the configurable HV

thresholds in the controller.

2. Toggle the ON/STBY switch

into the STBY position and
then back into the ON position.

3. If the problem is not corrected,

replace the rectifier.

Minor

RECTIFIER FAIL

ALM

TA

Thermal alarm:
•Excessive

ambient
temperature

•Internal

rectifier failure

1. Verify that there is no

obstruction of the fan inlet.

2. Toggle the ON/STBY switch

into the STBY position and
then back into the ON position.

3. If the problem is not corrected,

replace the rectifier.

Minor

RECTIFIER FAIL

ALM

FSE

Fuse alarm:
•DC fuse open
•Internal

rectifier failure

1. Toggle the ON/STBY switch

into the STBY position and
then back into the ON position.

2. If the problem is not corrected,

replace the rectifier.

Minor

RECTIFIER FAIL

ALM

LO

Low output
voltage:
•Excessive

output current

•Internal

rectifier failure

1. Toggle the ON/STBY switch

into the STBY position and
then back into the ON position.

2. If the problem is not corrected,

replace the rectifier.

Minor

RECTIFIER FAIL

ALM

ICS
IP5
IP6
IP7

Internal rectifier
failure

1. Place the ac circuit breaker for

the rectifier in the OFF
position.

2. Remove the rectifier from the

shelf.

3. Wait for 30 seconds or until all

front panel display LEDs have
extinguished.

4. Replace the rectifier.
5. Return the ac breaker to the

ON position.

6. Place the rectifier ON/STBY

switch into the ON position.

7. If the problem is not corrected,

replace the rectifier.

Table 14-E: Rectifier Related Alarms

(See Figures 12-6 and 12-8)

Controller

Alarm

Status

Vector

Controller Display

Rectifier

LED

Rectifier

Display

Possible

Problem(s)

Possible Solution(s)