GE Industrial Solutions GPS 4812_24 User Manual
Page 121
Galaxy Power System 4812/24
Issue 9 Januray 2008
Troubleshooting Vector Systems 14 - 9
Minor
RECTIFIER FAIL
ALM
HO
High output
voltage:
•Rectifier high
voltage
shutdown
•Internal
rectifier failure
1. Verify the configurable HV
thresholds in the controller.
2. Toggle the ON/STBY switch
into the STBY position and
then back into the ON position.
3. If the problem is not corrected,
replace the rectifier.
Minor
RECTIFIER FAIL
ALM
TA
Thermal alarm:
•Excessive
ambient
temperature
•Internal
rectifier failure
1. Verify that there is no
obstruction of the fan inlet.
2. Toggle the ON/STBY switch
into the STBY position and
then back into the ON position.
3. If the problem is not corrected,
replace the rectifier.
Minor
RECTIFIER FAIL
ALM
FSE
Fuse alarm:
•DC fuse open
•Internal
rectifier failure
1. Toggle the ON/STBY switch
into the STBY position and
then back into the ON position.
2. If the problem is not corrected,
replace the rectifier.
Minor
RECTIFIER FAIL
ALM
LO
Low output
voltage:
•Excessive
output current
•Internal
rectifier failure
1. Toggle the ON/STBY switch
into the STBY position and
then back into the ON position.
2. If the problem is not corrected,
replace the rectifier.
Minor
RECTIFIER FAIL
ALM
ICS
IP5
IP6
IP7
Internal rectifier
failure
1. Place the ac circuit breaker for
the rectifier in the OFF
position.
2. Remove the rectifier from the
shelf.
3. Wait for 30 seconds or until all
front panel display LEDs have
extinguished.
4. Replace the rectifier.
5. Return the ac breaker to the
ON position.
6. Place the rectifier ON/STBY
switch into the ON position.
7. If the problem is not corrected,
replace the rectifier.
Table 14-E: Rectifier Related Alarms
(See Figures 12-6 and 12-8)
Controller
Alarm
Status
Vector
Controller Display
Rectifier
LED
Rectifier
Display
Possible
Problem(s)
Possible Solution(s)