Galaxy Power System 4812/24

14 - 10 Troubleshooting Vector Systems

Issue 9 Januray 2008

Minor

RECTIFIER FAIL

ALM

SEN

Thermal sensor
failure:
•Internal

rectifier failure

1. Place the ac circuit breaker for

the rectifier in the OFF
position.

2. Remove the rectifier from the

shelf.

3. Wait for 30 seconds or until all

front panel display LEDs have
extinguished.

4. Replace the rectifier.
5. Return the ac breaker to the

ON position.

6. Place the rectifier ON/STBY

switch into the ON position.

7. If the problem is not corrected,

replace the rectifier with a new
one.

Minor

RECTIFIER FAIL

FAN ALM None

Fan failure

Replace the fan in the rectifier.

Minor

rect manual off

STBY

Blank

Rectifier has
been manually
turned off.

Turn rectifier on.

Minor

high float volt

None

None

Configuration
problem

Call technical support.

Table 14-E: Rectifier Related Alarms

(See Figures 12-6 and 12-8)

Controller

Alarm

Status

Vector

Controller Display

Rectifier

LED

Rectifier

Display

Possible

Problem(s)

Possible Solution(s)