Electromagnetic Flow Meter

FW: 842018/842009

Accuracy

According to the type and size of the flow sensor, the measuring accuracy
will be better than 0.25%, provided that the flow sensor has the correct
dimension.

1

2

3

4

5

[%]

0,2

0,1

0

0,5

2

1

5

10 m/s

Sizing

The flow sensor should be selected so the flow velocity through the sensor
will be between 0.2 - 10 m/s.
MJK recommends that flow velocities in tubes are kept between 1 - 3 m/s
for reliable and safe operation. See also the dimensioning table below and
the dimensioning chart on the following page.

Min and max flow

DN

Qmin

Qmax

DN

Qmin

Qmax

DN

Qmin

Qmax

0.2 m/s

10 m/s

0.2 m/s

10 m/s

0.2 m/s

10 m/s

[l/h]

[l/h]

[l/h]

[l/h]

[m

3

/h]

[m

3

/h]

3

5.09

254

20

226

11304

65

2,39

119

6

20.4

1018

25

353

17676

80

3,62

181

8

36.2

1810

32

579

28944

100

5,65

283

10

56.5

2827

40

905

45360

125

8,84

442

15

127

6362

50

1414

70560

150

12,7

636

Min and max flow

DN

Qmin

Qmax

DN

Qmin

Qmax

DN

Qmin

Qmax

0.2 m/s

10 m/s

0.2 m/s

10 m/s

0.2 m/s

10 m/s

[m

3

/h]

[m

3

/h]

[m

3

/h]

[m

3

/h]

[m

3

/h]

[m

3

/h]

200

22.6

1131

450

115

5726

900

458

22902

250

35.3

1767

500

141

7069

1000

565

28274

300

50.9

2545

600

204

10179

1200

814

40715

350

69.3

3464

700

277

13854

The Qmax. is equal to 20 mA

factory preset

400

90.5

4524

800

362

18095