Xylem Magflux Electromagnetic Flow Meter User Manual

Page 80

Advertising
background image

80

EN 3.05 MagFlux Manual 1212

Electromagnetic Flow Meter

Limitation of the automatic batch counter on DO 1 (Opto Relay)

The maximum limit is 500 pulses pr sec at 1 ms pulse length.

The formula for the minimum flow unit pr pulses is:

(flow at 20mA) x (pulse delay in mSec) / 1800000

Example: Min. flow unit/pulses for DN 100 max. flow 300 m3/h ?
Minimum flow unit pr pulses = 300 m

3

x 100 mSec / 1800000 =

0,016 m

3

which is rounded to 0,1 m

3

by the MagFlux.

The formula for the maximum flow unit pr pulses is:

(flow at 20mA)

Example: DN 100 max. flow 300 m

3

/h ?

Maximum flow unit pr pulses = 300 m

3

Limitation of the automatic batch counter on DO 2 (mech. relay)

The maximum limit is 120 pulses pr hour.

The formula for minimum flow unit pr pulses is:

(flow at 20mA) / 120

Example: DN 100 max. flow 300 m

3

/h ?

Minimum flow unit pr pulses = 300 / 120 = 2,5 m

3

The formula for maximum flow unit pr pulses is:

(flow at 20mA)

Example: DN 100 max. flow 300 m3/h ?
Maximum flow unit pr pulses = 300 m

3

Limitation of the manual and adaptive batch counter on DO 1 or DO 2

The formula for minimum flow unit pr pulses is:

(flow at 20mA) / 360

Example: DN 100 max. flow 300 m

3

/h ?

Minimum flow unit pr pulses = 300 / 360 = 0,833 m

3