Electromagnetic Flow Meter

FW: 842018/842009

Remote Flow Sensor

Connect the remote flow sensor to the flow converter with the included
cable (part number 691080).
Important: Do not use other cable types!
Important: Terminals 1 and 4 must be shunted!
The extension cable length between converter and sensor must under
normal circumstances not exceed 50 meters. Power lines running in paral-
lel and noisy environments may reduce the max. length to less than 50
meters. Consult MJK personnel for advice and guidance.

Remote Flow Sensor

691080

Terminal

Signal

Designation

Colour

before March 2011

Colour

from March 2011

1

Liquid GND

Shield

-

-

2

E1

Wire pair no. 1

Red

Red

3

E2

Wire pair no. 1

White

White

4

GND

Wire pair no. 3

Black

Black

5

L1

Wire pair no. 2

Green

Blue

6

L2

Wire pair no. 2

White

Brown

7, 8 and 9

not used

Converter Connection Board - Local

Red

White

Blac

k

Blue

Bro

wn

F

or attached

Displa

y Unit

F

or remote

Displa

y Unit

Digital output 1

DO

1

D

I

1

DO

2

Digital output

2

Digital input

10-30

V DC

4-20 mA output

P

ower supply

Electronic rela

y

max.

50

V DC 120 mA

Electromechanical rela

y

max.

50

V

A

C

/ 1

A

4-20 mA max.

800

Fuse rating:

125 mA

T @ 115

V

A

C

Connection for

Flow Sensor

63 mA

T @ 230

V

A

C