Xylem Magflux Electromagnetic Flow Meter User Manual

Page 20

Advertising
background image

20

EN 3.05 MagFlux Manual 1212

Electromagnetic Flow Meter

2. If it becomes necessary to use reducers, the inner angle must not

exceed 7.5°.

The minimum length to keep the angle below 7.5° can be checked by

means of the formula below:

L = (D - d) x 7.63

where "D" is the large diameter and "d" the small diameter of the re-

ducer.

Example: If a flow sensor in dimension DN 80 is mounted downstream

of a 100 mm pipe, the reducer must then have a length of minimum
152,6 mm in order to keep the inner angle below 7,5 °.

3. Flange connections must be assembled concentrically on both the up-

stream and the downstream side. Measuring accuracy will be affected
by turbulence in the liquid from poorly made connections.

Important: Gaskets and grounding rings must also be mounted con-

centrically!

4. The flow sensor should always be filled with liquid. For that reason the

flow sensor must not be mounted at the highest point of the pipe sys-
tem or in free outlets, where gravity could empty or partially empty the
pipe.