Burkert Type 8611 User Manual

Page 26

Advertising
background image

26

ElectricalInstallation

terminal block 3

terminal

configuration

external circuit

19

GND – Pt 100, RTD

(0 ... 200 °C)

19

20

Pt 100

20
(

AIN3)

(+) Pt 100, RTD (power supply)

21

GND – Analog input

21

A-GND

22
(

AIN1)

(+) Process value input
4 - 20 mA / 0 - 10 V

22
21

4 - 20 mA / 0 - 10 V (source)

A-GND

23

GND – Sensor, actuating element

23

GND

24

24 V DC sensor supply or
actuating element

24
23

24 V DC - Out (max. 1 A)

GND

25

Supply of
Type 8611

(

DIN3)

Frequency input 2
(NPN or PNP)

Q

2

for ratio control

(

MODE = RATI)

Jumper 2

NPN

PNP

Transmitter

12 or 24

24 V DC

GND

11 or 23

Clock

25

Supply of 8611

25

External
supply

(

DIN3)

Frequency input 2
(NPN or PNP)

Q

2

for ratio control

(

MODE = RATI)

Jumper 2

NPN

PNP

Transmitter

GND

11 or 23

GND

Supply

Clock

25

External supply

26

(

DIN2)

(+) Binary input

26

1, 11, or 23

0 ... 2.7 V (log. 0)
3 ... 30 V (log. 1)

max. 1 kHz

GND

27

Supply of
Type 8611

(

DIN1)

Frequency input 1
(NPN or PNP)

Actual value flow-rate /
Q

1

for ratio control

(

MODE = RATI)

Jumper 1

NPN

PNP

Transmitter

12 or 24

24 V DC

GND

11 or 23

Clock

27

Supply of 8611

27

External
supply

(

DIN1)

Frequency input 1
(NPN or PNP)

Actual value flow-rate /
Q

1

for ratio control

(

MODE = RATI)

Jumper 1

NPN

PNP

Transmitter

GND

11 or 23

GND

Supply

Clock

27

External supply

Table 11:

Configuration of terminal block 3

english

Type 8611