FunctionsoftheConfigurationLevel

display

description

POS

Output of actuating element position (only for actuating element type

MODE = SCV)

Value range: 000.0 - 100.0

000.0 = valve closed
100.0 = valve open

Q1

Output of flow-rate Q1 for ratio control (control variable

MODE = RATI)

Q2

Output of flow-rate Q2 for ratio control (control variable

MODE = RATI)

RFAC

Output of ratio factor

RFAC for ratio control (control variable MODE = RATI)

Scaling: Fixed scaling between 0.000 and 9.999.

4 mA / 20 mA Scaling of 4 - 20 mA output signal.

4 mA: Entry of output value for 4 mA

20 mA: Entry of output value for 20 mA
Value range: Output value for 4 mA < output value for 20 mA or

output value for 20 mA < output value for 4 mA

0 V / 10 V

Scaling of 0 - 10 V output signal.

0 V: Entry of output value for 0 V
10 V: Entry of output value for 10 V

Value range: Output value for 0 V < output value for 10 V or

output value for 10 V < output value for 0 V