83

FunctionsoftheConfigurationLevel

12.15.1.

PULS - configuration of the binary output as pulse output

In this menu, it can be defined when, referred to a specific flow-rate volume, a pulse signal is to be emitted.

The measuring units and the volume per pulse can be selected as followed:

DM3

Cubic decimeters (liters)

IGAL

British gallon (Imperial)

UGAL

American gallon

M3

Cubic meters

PU

Flow-rate volume per pulse (number of pulses) related to selected measuring unit

Table 31:

Measuring units for pulse output

setting aid:

Selection of the number of pulses:

The pulse frequency f

pu

is calculated according to the equation

Q (flow-rate)

PU (number of pulses)

f

pu

=

The pulse frequency may never exceed the frequency of 150 Hz. Select the number of pulses PU so that
you obtain a max. frequency of 150 Hz for the maximum flow-rate.
A clock ratio of 50 % is emitted over the entire frequency range.

Setting in the menu:

NO

PULS

LIMT

2_P

B_O2

B_O1

DM3

IGAL

UGAL

M3

000.0

PU

1

DP V

0.1

DP V

0.01

DP V

For description of the configuration

see “12.15.3. 2_P - Configuration of the binary output as

2-state controller”

For description of the configuration

see “12.15.2. LIMT - Configuration of the binary output as limit switch”

Figure 61:

B_O1; Configuration of the binary output as pulse output

english

Type 8611