FunctionsoftheConfigurationLevel

display SETP

description

INT

Internal set-point value default.
Is entered in the operating state MANUAL in the

SET menu using the keyboard.

See chapter “11.5. SET - Set-point value default for process control”

EXT

External process set-point value default using standard signal (4 - 20 mA or 0 - 10 V).

4 mA / 20 mA

Scaling of 4 - 20 mA standard signal (for definition of decimal places see

UNIT menu).

0 V / 10 V

Scaling of 0 - 10 V standard signal (for definition of decimal places see

UNIT menu).

Table 20:

Display SETP

Setting in the menu for ratio control (

RFAC):

S_IN

AOUT

RFAC

0000

4 mA

*

)

9.999

20 mA

*

)

0000

0 V

*

)

9.999

10 V

*

)

INT

EXT

Selection of standard signal

4 – 20

0 – 10

Scaling

Selection of
set-point value default

*

)

The display depends on the selection
of the standard signal

Figure 48:

RFAC; Setting the ratio factor

display
RFAC

description

INT

Internal ratio factor default.
Is entered in the operating state MANUAL in the

RFAC menu using the keyboard.

See chapter “11.6. RFAC - Ratio factor default for ratio control”.

Value range: 0.000 to 9.999

EXT

External ratio factor default (

RFAC) using standard signal (4 - 20 mA or 0 - 10 V).

4 mA / 20 mA

Scaling of 4 - 20 mA standard signal (value range: 0.000 - 9.999).

0 V / 10 V

Scaling of 0 - 10 V standard signal (value range: 0.000 - 9.999).

Table 21:

Display RFAC

The decimal place for the ratio factor

RFAC is fixed and cannot be changed.

english

Type 8611