Burkert Type 8611 User Manual

Page 80

Advertising
background image

80

FunctionsoftheConfigurationLevel

display
INV

description

NO

Not inverted or direct control (the process value increases with the opening of the valve)

YES

Inverted control (the process value decreases with the opening of the valve)

Figure 57:

Display INV

12.13.9.

ZERO – zero point shut-off

The zero point shut-off can be activated or deactivated. When the zero point shut-off is activated it is ensured
that the valves close securely.

display
ZERO

description

NO

No zero point shut-off. The control is continuous up to the lower limit value of the value
range defined in

SETP-EXT (see chapter 12.5) or up to the lower limit of the range

defined in

VALV-MIN (see chapter 12.17). The greater one of the two values is relevant

YES

Zero point shut-off is active. The control is continuous until the set-point value < 2% of
the upper value range of

SETP-EXT has been reached.

If the 2% limit is not reached, all valve outputs are disconnected from the voltage
supply. When valves are controlled with 0 - 10 V or 4 - 20 mA, the control signal is set
to 0 V or 4 mA.

Figure 58:

Display ZERO

12.13.10.

STRT – start value for active control

A start value can be defined for continuous actuating elements; this start value is approached immediately by the
actuating element when the control is started.
If the working point of the control valve is known, this can be set as start value. The working point of the valve is
then controlled very quickly. Depending on the selected actuating element, the following selection options are
available:

selected actuating element

value range

Solenoid control valve (

SCV), open/closed valve (2P - T, 3P - T)

0 % - 100 %

Control valve with 0 - 10 V control (

0 – 10)

0 V – 10 V

Control valve with 4 - 20 mA control

(4 – 20)

4 mA – 20 mA

Figure 59:

Start value setting

english

Type 8611