FunctionsoftheConfigurationLevel

Setting the quasi-continuous 3-state control in the menu:

0001

TMN1

Selection of
control variable

MODE

0001

CODE

selection of operating principle and enter minimum control time

selection of
three-state control

Continue with
selection of process value input
see Figure 27

3P – T

NC

VLV2

NC

VLV1

NO

VLV2

NO

VLV1

0001

TMN2

Figure 43:

3P – T; 3-state control / operating principle

display

description

3P – T

Quasi-continuous 3-state control with time-proportional control for opening and closing.

VLV1

Control of valve 1 or "Open" motor valve (output

BO3)

VLV2

Control of valve 2 or "Close" motor valve (output

BO4)

NC

Valve with operating principle "closed with no current" (normally closed).
In the event of a motor drive, the NC operating principle must be set for both

VLV1 and VLV2.

NO

Valve with operating principle "opened with no current" (normally open).

TMN1 Minimum control time of valve 1 in ms.
TMN2 Minimum control time of valve 2 in ms.

Table 18:

Display 3P – T; quasi-continuous 3-state control / operating principle